CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-89
2
" 6646 Field Current -9999.999 to
9999.999
--- 0.001 F004 0
" 6648 Field Current Units --- --- --- F206 "A"
Accidental Energization (Read/Write Grouped Setting)
G30, G60 6650 Accidental Energization Function 0 to 1 --- 1 F102 0 (Disabled)
" 6651 Accidental Energization Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6652 Accidental Energization Arming Mode 0 to 1 --- 1 F193 0 (UV AND
OFFLINE)
" 6653 Accidental Energization OC Pickup 0.02 to 3 pu 0.001 F003 300
" 6655 Accidental Energization UV Pickup 0.004 to 3 pu 0.001 F003 500
" 6657 Accidental Energization Offline 0 to 4294967295 --- 1 F300 0
" 6659 Accidental Energization Block 0 to 4294967295 --- 1 F300 0
" 665B Accidental Energization Target 0 to 2 --- 1 F109 0 (Self-reset)
" 665C Accidental Energization Events 0 to 1 --- 1 F102 0 (Disabled)
" 665D Reserved (5 items) 0 to 65535 --- 1 F001 0
Loss of Excitation (Read/Write Grouped Setting)
G30, G60 666A Loss Of Excitation Function 0 to 1 --- 1 F102 0 (Disabled)
" 666B Loss Of Excitation Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
" 666C Loss Of Excitation Center 1 0.1 to 300 ohm 0.01 F001 1000
" 666D Loss Of Excitation Radius 1 0.1 to 300 ohm 0.01 F001 800
" 666E Loss Of Excitation UV Supervision Enable 1 0 to 1 --- 1 F102 1 (Enabled)
" 666F Loss Of Excitation Pickup Delay 1 0 to 65.535 s 0.001 F001 50
" 6670 Loss Of Excitation Center 2 0.1 to 300 ohm 0.01 F001 1200
" 6671 Loss Of Excitation Radius 2 0.1 to 300 ohm 0.01 F001 1000
" 6672 Loss Of Excitation UV Supervision Enable 2 0 to 1 --- 1 F102 1 (Enabled)
" 6673 Loss Of Excitation Pickup Delay 2 0 to 65.535 s 0.001 F001 500
" 6674 Loss Of Excitation UV Supervision 0 to 1.25 pu 0.001 F001 700
" 6675 Loss Of Excitation Block 0 to 4294967295 --- 1 F300 0
" 6677 Loss Of Excitation Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6678 Loss Of Excitation Events 0 to 1 --- 1 F102 0 (Disabled)
" 6679 Reserved (5 items) 0 to 65535 --- 1 F001 0
Bus Configuration (Read/Write Setting) (6 Modules)
B90 667E ...Repeated for Bus Zone 3
Sensitive Directional Power (Read/Write Grouped Setting) (2 Modules)
C60, D60, F60,
G30, G60, L90,
M60, N60, T60
6680 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6681 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6682 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 0
" 6683 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 0
" 6684 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 100
" 6685 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 50
" 6686 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 100
" 6687 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000
" 6688 Sensitive Directional Power 1 Block 0 to 4294967295 --- 1 F300 0
" 668A Sensitive Directional Power 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 668B Sensitive Directional Power 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 668C Reserved (5 items) 0 to 65535 --- 1 F001 0
Products Address Register name Range Units Step Format Default