CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-91
2
" 66E7 Reserved (4 items) 0 to 65535 --- 1 F001 0
Generator Unbalance (Read/Write Grouped Setting)
G30, G60 66F0 Generator Unbalance Function 0 to 1 --- 1 F102 0 (Disabled)
" 66F1 Generator Unbalance Source 0 to 5 --- 1 F167 0 (SRC 1)
" 66F2 Generator Unbalance Inom (rated full load
current of the machine)
0 to 1.25 pu 0.001 F001 800
" 66F3 Generator Unbalance Stage 1 Pickup 0 to 100 % 0.01 F001 800
" 66F4 Generator Unbalance Stage 1 K value 0 to 100 --- 0.01 F001 100
" 66F5 Generator Unbalance Stage 1 Tmin 0 to 50 s 0.001 F001 250
" 66F6 Generator Unbalance Stage 1 Tmax 0 to 1000 s 0.1 F001 6000
" 66F7 Generator Unbalance Stage 1 K Reset 0 to 1000 s 0.1 F001 2400
" 66F8 Generator Unbalance Stage 2 Pickup 0 to 100 % 0.01 F001 300
" 66F9 Generator Unbalance Stage 2 Pickup Delay 0 to 1000 s 0.1 F001 50
" 66FA Generator Unbalance Block 0 to 4294967295 --- 1 F300 0
" 66FC Generator Unbalance Target 0 to 2 --- 1 F109 0 (Self-reset)
" 66FD Generator Unbalance Events 0 to 1 --- 1 F102 0 (Disabled)
" 66FE Reserved (3 items) 0 to 65535 --- 1 F001 0
Stator Ground Source (Read/Write Grouped Setting)
G30, G60 670A Stator Ground Source 0 to 5 --- 1 F167 0 (SRC 1)
Subharmonic Stator Ground (Read/Write Grouped Setting)
G60 6710 Subharmonic Stator Ground Function 0 to 1 --- 1 F102 0 (Disabled)
" 6711 Subharmonic Stator Ground Stage 1 Pickup 1 to 20 kOhm 1 F001 10
" 6712 Subharmonic Stator Ground Stage 1 Pickup
Delay
0.1 to 600 s 0.1 F001 100
" 6713 Subharmonic Stator Ground Stage 2 Pickup 1 to 20 kOhm 1 F001 3
" 6714 Subharmonic Stator Ground Stage 2 Pickup
Delay
0.1 to 600 s 0.1 F001 10
" 6715 Subharmonic CT Angle Compensation -30 to 30 degrees 0.1 F002 0
" 6718 Subharmonic Stator Ground OC Pickup 0.001 to 1 pu 0.001 F001 10
" 6719 Subharmonic Stator Ground OC Delay 0.1 to 600 s 0.01 F001 100
" 671A Subharmonic Stator Ground Volt Supv 0 to 0.1 pu 0.001 F001 0
" 671B Subharmonic Stator Ground Curr Supv 0 to 0.1 pu 0.001 F001 0
" 671C Subharmonic Stator Ground Block 0 to 4294967295 --- --- F300 0
" 671E Subharmonic Stator Ground Events 0 to 1 --- 1 F102 0 (Disabled)
" 671F Subharmonic Stator Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
Stator Ground (Read/Write Grouped Setting)
G30, G60 6720 Stator Ground Function 0 to 1 --- 1 F102 0 (Disabled)
" 6721 Stator Ground Stage 1 Pickup 0 to 0.9 pu 0.001 F001 150
" 6722 Stator Ground Stage 1 Pickup Delay 0 to 600 s 0.01 F001 100
" 6723 Stator Ground Stage 1 Supv 0.001 to 0.1 pu 0.000
1
F001 57
" 6724 Stator Ground Stage 2 Pickup 0 to 0.9 pu 0.001 F001 150
" 6725 Stator Ground Stage 2 Pickup Delay 0 to 600 s 0.01 F001 0
" 6726 Stator Ground Stage 2 Supv 0.001 to 0.1 pu 0.000
1
F001 45
" 6727 Stator Ground Block 0 to 4294967295 --- 1 F300 0
" 6729 Stator Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
" 672A Stator Ground Event 0 to 1 --- 1 F102 0 (Disabled)
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30