2-92 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 672B Reserved (5 items) 0 to 65535 --- 1 F001 0
Split Phase Protection (Read/Write Grouped Setting)
G30, G60 6730 Split Phase Protection Function 0 to 1 --- 1 F102 0 (Disabled)
" 6731 Split Phase Protection Source 0 to 5 --- 1 F167 0 (SRC1)
" 6732 Split Phase Protection Load Source 0 to 5 --- 1 F167 0 (SRC1)
" 6733 Split Phase Protection Phase A Pickup 0.02 to 1.5 pu 0.001 F001 200
" 6734 Split Phase Protection Phase A Offset 0 to 1 pu 0.001 F001 0
" 6735 Split Phase Protection Phase A Slope 0 to 100 % 0.1 F001 0
" 6736 Split Phase Protection Phase B Pickup 0.02 to 1.5 pu 0.001 F001 200
" 6737 Split Phase Protection Phase B Offset 0 to 1 pu 0.001 F001 0
" 6738 Split Phase Protection Phase B Slope 0 to 100 % 0.1 F001 0
" 6739 Split Phase Protection Phase C Pickup 0.02 to 1.5 pu 0.001 F001 200
" 673A Split Phase Protection Phase C Offset 0 to 1 pu 0.001 F001 0
" 673B Split Phase Protection Phase C Slope 0 to 100 % 0.1 F001 0
" 673C Split Phase Protection Minimum Load 0 to 1 pu 0.01 F001 0
" 673D Split Phase Protection Mode 0 to 1 --- 1 F225 0 (Over)
" 673E Split Phase Protection Delay 0 to 65.535 s 0.001 F001 0
Bus Configuration (Read/Write Setting) (6 Modules)
B90 673E ...Repeated for Bus Zone 5
Split Phase Protection (Read/Write Grouped Setting)
G30, G60 673F Split Phase Protection Block 0 to 4294967295 --- 1 F300 0
" 6741 Split Phase Protection Target 0 to 2 --- 1 F109 0 (Self-Reset)
" 6742 Split Phase Protection Events 0 to 1 --- 1 F102 0 (Disabled)
" 6743 Reserved (6 items) 0 to 65535 --- 1 F001 0
Reduced Voltage Starting (Read/Write Setting)
M60 6750 Reduced Voltage Start Function 0 to 1 --- 1 F102 0 (Disabled)
" 6751 Reduced Voltage Start Transition Mode 0 to 2 --- 1 F095 0 (Current
Only)
" 6752 Reduced Voltage Start FLA (full load
current)
25 to 300 % 1 F001 125
" 6753 Reduced Voltage Start Timer 1 to 600 s 0.1 F001 100
" 6754 Reduced Voltage Start Block 0 to 4294967295 --- 1 F300 0
" 6756 Reduced Voltage Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6757 Reduced Voltage Start Event 0 to 1 --- 1 F102 0 (Disabled)
" 6758 Reserved (5 items) 0 to 1 --- 1 F001 0
Trip Output (Read/Write Setting)
C60, D60, L60,
L90
6760 Trip Mode 0 to 2 --- 1 F195 0 (Disabled)
" 6761 Trip 3-Pole Input1 0 to 4294967295 --- 1 F300 0
" 6763 Trip 3-Pole Input2 0 to 4294967295 --- 1 F300 0
" 6765 Trip 3-Pole Input3 0 to 4294967295 --- 1 F300 0
" 6767 Trip 3-Pole Input4 0 to 4294967295 --- 1 F300 0
" 6769 Trip 3-Pole Input5 0 to 4294967295 --- 1 F300 0
" 676B Trip 3-Pole Input6 0 to 4294967295 --- 1 F300 0
" 676D Trip 1-Pole Input1 0 to 4294967295 --- 1 F300 0
" 676F Trip 1-Pole Input2 0 to 4294967295 --- 1 F300 0
" 6771 Trip 1-Pole Input3 0 to 4294967295 --- 1 F300 0
" 6773 Trip 1-Pole Input4 0 to 4294967295 --- 1 F300 0