CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-109
2
" 7238 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7239 Neutral Directional Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 723B Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 723C Neutral Directional Overcurrent 1 Polarizing
Voltage
0 to 1 --- 1 F231 0
(Calculated
V0)
" 723D Neutral Directional Overcurrent 1 Op
Current
0 to 1 --- 1 F196 0
(Calculated
3I0)
" 723E Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
" 723F Neutral Directional Overcurrent 1 Pos Seq
Restraint
0 to 0.5 --- 0.001 F001 63
" 7240 Reserved 0 to 1 --- 1 F001 0
D30, D60, F60,
G30, G60, L30,
L60, L90, M60,
N60, T60
7241 ...Repeated for Neutral Directional
Overcurrent 2
N60, T60 7252 ...Repeated for Neutral Directional
Overcurrent 3
Negative-Sequence Directional Overcurrent (Read/Write Grouped Settings) (2 or 3 Modules)
C70, D30, D60,
F60, G30, G60,
L60, L90, T60
72A0 Negative Sequence Directional Overcurrent
1 Function
0 to 1 --- 1 F102 0 (Disabled)
" 72A1 Negative Sequence Directional Overcurrent
1 Source
0 to 5 --- 1 F167 0 (SRC 1)
" 72A2 Negative Sequence Directional Overcurrent
1 Type
0 to 1 --- 1 F179 0 (Neg
Sequence)
" 72A3 Neg Sequence Directional Overcurrent 1
Forward ECA
0 to 90 ° Lag 1 F002 75
" 72A4 Neg Seq Directional Overcurrent 1 Forward
Limit Angle
40 to 90 degrees 1 F001 90
" 72A5 Neg Sequence Directional Overcurrent 1
Forward Pickup
0.015 to 30 pu 0.005 F001 50
" 72A6 Neg Seq Directional Overcurrent 1 Reverse
Limit Angle
40 to 90 degrees 1 F001 90
" 72A7 Neg Sequence Directional Overcurrent 1
Reverse Pickup
0.015 to 30 pu 0.005 F001 50
" 72A8 Negative Sequence Directional Overcurrent
1 Target
0 to 2 --- 1 F109 0 (Self-reset)
" 72A9 Negative Sequence Directional Overcurrent
1 Block
0 to 4294967295 --- 1 F300 0
" 72AB Negative Sequence Directional Overcurrent
1 Events
0 to 1 --- 1 F102 0 (Disabled)
" 72AC Negative Sequence Directional Overcurrent
1 Offset
0 to 250 ohms 0.01 F001 0
" 72AD Negative Sequence Directional Overcurrent
1 Pos Seq Restraint
0 to 0.5 --- 0.001 F001 63
" 72AE Reserved (3 items) 0 to 1 --- 1 F001 0
" 72B1 ...Repeated for Neg Seq Directional
Overcurrent 2
T60 72C2 ...Repeated for Neg Seq Directional
Overcurrent 3
Breaker Arcing Current Settings (Read/Write Setting) (2, 3, 4, or 6 Modules)