" A880 Blocking 1 Scheme 1P Rx3 0 to 4294967295 --- 1 F300 0
" A882 Blocking 1 Scheme 1P Rx4 0 to 4294967295 --- 1 F300 0
" A884 Blocking 1 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" A885 Blocking 1 1P Event 0 to 1 --- 1 F102 0 (Disabled)
Pilot POTT3 (Read/Write Setting)
F60 A886 POTT3 Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" A887 POTT3 Scheme Block 0 to 4294967295 --- 1 F300 0
" A889 POTT3 Dir Fwd1 0 to 4294967295 --- 1 F300 0
" A88B POTT3 Dir Fwd2 0 to 4294967295 --- 1 F300 0
" A88D POTT3 Dir Fwd3 0 to 4294967295 --- 1 F300 0
" A88F POTT3 Rx 0 to 4294967295 --- 1 F300 0
" A891 POTT3 Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" A892 POTT3 Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 20
" A893 POTT3 Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A894 POTT3 Seal In Delay 0 to 65.535 s 0.001 F001 400
" A895 POTT3 Line End Open 0 to 4294967295 --- 1 F300 0
" A897 POTT3 Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
" A898 POTT3 Permissive Echo 0 to 1 --- 1 F102 0 (Disabled)
" A899 POTT3 Echo Duration 0 to 65.535 s 0.001 F001 100
" A89A POTT3 Echo Lockout 0 to 65.535 s 0.001 F001 250
" A89B POTT3 Target 0 to 2 --- 1 F109 0 (Self-reset)
" A89C POTT3 Events 0 to 1 --- 1 F102 0 (Disabled)
Pilot DCB3 (Read/Write Setting)
F60 A89D DCB3 Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" A89E DCB3 Scheme Block 0 to 4294967295 --- 1 F300 0
" A8A0 DCB3 Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
" A8A1 DCB3 Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 30
" A8A2 DCB3 Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A8A3 DCB3 Scheme Seal In Delay 0 to 65.535 s 0.001 F001 10
" A8A4 DCB3 Dir Fwd1 0 to 4294967295 --- 1 F300 0
" A8A6 DCB3 Dir Fwd2 0 to 4294967295 --- 1 F300 0
" A8A8 DCB3 Dir Fwd3 0 to 4294967295 --- 1 F300 0
" A8AA DCB3 Dir Rev1 0 to 4294967295 --- 1 F300 0
" A8AC DCB3 Dir Rev2 0 to 4294967295 --- 1 F300 0
" A8AE DCB3 Dir Rev3 0 to 4294967295 --- 1 F300 0
" A8B0 DCB3 Force Tx Stop1 0 to 4294967295 --- 1 F300 0
" A8B2 DCB3 Force Tx Stop2 0 to 4294967295 --- 1 F300 0
" A8B4 DCB3 Rx 0 to 4294967295 --- 1 F300 0
" A8B6 DCB3 Scheme Target 0 to 2 --- 1 F109 0 (Self-reset)
" A8B7 DCB3 Scheme Events 0 to 1 --- 1 F102 0 (Disabled)
Frequency Rate of Change (Read/Write Setting) (2 or 4 Modules)
D30, D60, F60,
G30, G60, L30,
L90, N60, T60
A900 Frequency Rate of Change 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" A901 Frequency Rate of Change 1 OC
Supervision
0.02 to 30 pu 0.001 F001 200
" A902 Frequency Rate of Change 1 Min 20 to 80 Hz 0.01 F001 4500
" A903 Frequency Rate of Change 1 Max 20 to 80 Hz 0.01 F001 6500