2-208 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
F243
ENUMERATION: FIELD UNIT TYPE
0 = CC-05, 1 = CV-05, 2 = CC-01, 3 = CV-01
F244
ENUMERATION: FIELD UNIT PROCESS CARD PORT
0 = H4a, 1 = H4b 2 = H3a, 3 = H3b, 4 = H2a, 5 = H2b, 6 = H1a, 7 =
H1b
F245
ENUMERATION: TEST MODE FUNCTION
F246
ENUMERATION: BRICK TRANSDUCER RANGE
F247
ENUMERATION: BRICK AC BANK ORIGIN
F248
ENUMERATION: BRICK AUX AC BANK ORIGIN
F250
ENUMERATION: B90 PRODUCT FUNCTION
0 = Logic, 1 = Protection
F253
ENUMERATION: BRICK TRANSDUCER ORIGIN
Value Instance
0 Disabled
1Isolated
2Forcible
Value Description
0 -5...5V
1 -1...1mA
2 0...1mA
3 0...-1mA
4 0...5mA
5 0...10mA
6 0...20mA
7 4...20mA
8 potentiometer
9tap position
Value Description
0None
1 U1/AC1..3
2 U1/AC5..7
3 U2/AC1..3
4 U2/AC5..7
5 U3/AC1..3
6 U3/AC5..7
7 U4/AC1..3
8 U4/AC5..7
9 U5/AC1..3
10 U5/AC5..7
11 U6/AC1..3
12 U6/AC5..7
13 U7/AC1..3
14 U7/AC5..7
15 U8/AC1..3
16 U8/AC5..7
Value Description
0None
1U1/AC4
2U1/AC8
3U2/AC4
4U2/AC8
5U3/AC4
6U3/AC8
7U4/AC4
8U4/AC8
9U5/AC4
10 U5/AC8
11 U6/AC4
12 U6/AC8
13 U7/AC5
14 U7/AC8
15 U8/AC5
16 U8/AC8
Value Description
0None
1U1/DC1
2U1/DC2
3U1/DC3
4U2/DC1
5U2/DC2
6U2/DC3
↓↓
24 U8/DC3
Value Description