CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-209
2
F254
ENUMERATION: INCIPIENT CABLE FAULT MODE
F255
ENUMERATION: CAPACITOR BANK GROUNDING
F256
ENUMERATION: BRICK ORIGIN/DESTINATION
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equipment
Mismatch, 4 = Brick Trouble
F270
ENUMERATION: FAULT REPORT VT SUBSTITUTION
F281
ENUMERATION: BREAKER/SWITCH PACKED STATES BIT POSI-
TIONS
F282
ENUMERATION: BREAKER/SWITCH COMMAND
F300
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type)
Value Function
0 Number of Counts
1 Counts per Window
Value Description
0 VT (ungrnd) = ungrounded
1 CTxR (grnd) = grounded
Value Description
0None
1U1
2U2
3U3
4U4
5U5
6U6
7U7
8U8
Value Description
0None
1I0
2V0
Value Description
0Closed Bit
1Open Bit
2Discrep Bit
3Ph A Interm Bit
4Ph B Interm Bit
5Ph C Interm Bit
6Bad Status Bit
7 OOS Bit
8 Tagged Bit
9Subd Clsd Bit
10 Subd Open Bit
11 Bypassed Bit
12 Blk Rcls Bit
13 Ar Armed Bit
14 Racked In Bit
15 Trouble Bit
Value Description
0Cancel
1Open
2Close
3Tag
4Untag
5 Substitute Closed
6 Substitute Open
7 Remove Substitution
8 Bypass
9 Remove Bypass
10 Block Autoreclose
11 Unblock Autoreclose