CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-33
3
RsStat SPC Mapped to command CLEAR ALL RELAY R/Ctrl
pulseConfig PulseConfig CF R
pulseConf ig
ENUMERATED 0 (pulse) R
pulseConfig.onD INT32 0 indicates the duration is locally R
pulseConf ig
INT32 0 R
pulseConf ig
INT32 1 R
ctlModel CtlModels CF
LPHD1.RsStat
.ctlModel 1, the code for direct control with normal
security; 2 is code for SBO with normal
security; 0 is for status only according to
IEC 61850-7-2. Enhanced security is not
supported as there is no means of
confirming successful execution of the
R/C
sboT
imeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operT
imeout INT32U CF 0 R
Sim SPC Will accept simulated GOOSE messages R
stVal BOOLEAN ST R
ctlModel CtlModels CF 0 R/C
MMSConne
cts
MV Number of MMS client connections active R
mag AnalogueValue MX R
mag.i INT32 5 minus the value of “MMS TCP(max 5)” R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
sVC ScaledValue CF R
sVC.scaleFactor FLOAT32 1 R
sVC.offset FLOAT32 0 R
AnyErr SPS ANY SELF TESTS operand R
stVal BOOLEAN ST ANY SELF TESTS R
MajorErr SPS ANY MAJOR ERROR operand R
stVal BOOLEAN ST ANY MAJOR ERROR R
MinorErr SPS ANY MINOR ERROR operand R
stVal BOOLEAN ST ANY MINOR ERROR R
BatFail SPS BATTERY FAIL operand R
stVal BOOLEAN ST BATTERY FAIL R
ClkUnsync
h
SPS CLOCK UNSYNCHRONIZED operand R
stVal BOOLEAN ST CLOCK UNSYNCHRONIZED R
RlyUTCTms
SPS
relay UTC time in seconds
R
stVal BOOLEAN ST Modbus register 41A0h value,
i.e., “Relay time clock set time”
register value after converting to
UTC
R
DrcDevOff SPS DIRECT DEVICE OFF operand R
stVal BOOLEAN ST DIRECT DEVICE OFF R
DrcRingBrk SPS DIRECT RING BREAK operand R
stVal BOOLEAN ST DIRECT RING BREAK R
LNName: LPHD1LDevice inst: MasterUR element:
data obj. data attribute Type FC UR Name Description R/W/C