EasyManua.ls Logo

GE b30 - 5.6 GROUPED ELEMENTS

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-34 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
EqpMismat SPS EQUIPMENT MISMATCH operand R
stVal BOOLEAN ST EQUIPMENT MISMATCH R
FlexErrTkn SPS FLEXLOGIC ERR TOKEN operand R
stVal BOOLEAN ST FLEXLOGIC ERR TOKEN R
IrigbFail SPS IRIG-B FAILURE operand R
stVal BOOLEAN ST IRIG-B FAILURE R
LatchErr SPS LATCHING OUT ERROR operand R
stVal BOOLEAN ST LATCHING OUT ERROR R
OscilGOOS
E
SPS Oscillatory GOOSE operand R
stVal BOOLEAN ST Oscillatory GOOSE R
FrstEthFail SPS FIRST ETHERNET FAIL operand R
stVal BOOLEAN ST FIRST ETHERNET FAIL R
PtpFail SPS PTP FAILURE operand R
stVal BOOLEAN ST PTP FAILURE R
RxGooseOf
f
SPS RxGOOSE OFF operand R
stVal BOOLEAN ST RxGOOSE OFF R
RrtdComFa
il
SPS RRTD COMM FAIL operand R
stVal BOOLEAN ST RRTD COMM FAIL R
SecEthFail SPS SECOND ETHERNET FAIL operand R
stVal BOOLEAN ST SECOND ETHERNET FAIL R
ThrdEthFail SPS THIRD ETHERNET FAIL operand R
stVal BOOLEAN ST THIRD ETHERNET FAIL R
SntpFail SPS SNTP FAILURE operand R
stVal BOOLEAN ST SNTP FAILURE R
SysExcp SPS SYSTEM EXCEPTION operand R
stVal BOOLEAN ST SYSTEM EXCEPTION R
TempMnt SPS TEMP MONITOR operand R
stVal BOOLEAN ST TEMP MONITOR R
UNotPrgm SPS UNIT NOT PROGRAMMED operand R
stVal BOOLEAN ST UNIT NOT PROGRAMMED R
ProcBusFai
l
SPS PROCESS BUS FAILURE operand R
stVal BOOLEAN ST PROCESS BUS FAILURE R
ProcBusTr
b
l
SPS PROCESS BUS TROUBLE operand R
stVal BOOLEAN ST PROCESS BUS TROUBLE R
VoltMntr SPS VOLTAGE MONITOR operand R
stVal BOOLEAN ST VOLTAGE MONITOR R
BrckTrbl SPS BRICK TROUBLE operand R
stVal BOOLEAN ST BRICK TROUBLE R
RtdTrbl SPS RTD TROUBLE operand R
stVal BOOLEAN ST RTD TROUBLE R
TdrTrbl SPS TDR TROUBLE operand R
stVal BOOLEAN ST TDR TROUBLE R
InRef1 ORG PROCESS BUS FAILURE setting. R
setSrcRef ObjectReference SP PROCESS BUS FAILURE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: LPHD1LDevice inst: MasterUR element:
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals