CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-47
3
3.5.2.14 Capacitor bank phase overvoltage (CPhOv)
This element is instantiated in the following products: C70.
stVal BOOLEAN ST BUS # SAT θ R
DifAClc WYE Phase differential currents R
phsθ CMV R
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 BUS # DIFF Iθd magnitude, in
primary amps
R
phsθ.instCVal.ang
.f
FLOAT32 BUS # DIFF UR range -180...+180 converted to 0...360R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 BUS # DIFF Iθd magnitude, in
primary amps, with deadband
R
phsθ.cVal.ang.f FLOAT32 BUS # DIFF UR range -180...+180 converted to 0...360R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 5, the code for amps R
phsθ.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsθ.db INT32U CF BusDifPDIF#.DifAClc.phsθ.db R/W/C
phsθ.dbAng INT32U CF BusDifPDIF#.DifAClc.phsθ.dbAng R/W/C
phsθ.zeroDb INT32U CF R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA WYE Phase restraint currents R
phsθ CMV R
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 BUS # REST Iθr magnitude, in
primary amps
R
phsθ.instCVal.ang
.f
FLOAT32 BUS # REXT UR range -180...+180 converted to 0...360R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 BUS # REST Iθr magnitude, in
primary amps, with deadband
R
phsθ.cVal.ang.f FLOAT32 BUS # REST UR range -180...+180 converted to 0...360R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 5, the code for amps R
phsθ.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsθ.db INT32U CF BusDifPDIF#.DifAClc.phsθ.db R/W/C
phsθ.dbAng INT32U CF BusDifPDIF#.DifAClc.phsθ.dbAng R/W/C
phsθ.zeroDb INT32U CF R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
InRef2τ ORG BUS ZONE #τ STATUS setting. R
setSrcRef ObjectReference SP BUS ZONE #τ STATUS setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG BUS ZONE # DIFF BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP BUS ZONE # DIFF BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: BusDifPDIF# LDevice inst: Prot UR element: Bus Differential element # (ANSI 87B)
data obj. data attribute Type FC UR Name Description R/W/C