3-48 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-32: C70 capacitor bank phase overvoltage function data objects
LNName: CPhOvPTOV# LDevice inst: Prot UR element: BANK OVERVOLTAGE element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD BANK OV # PKP operands (including
individual three phases), which indicates
element will operate when delay expires.
R
general BOOLEAN ST BANK OV # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsA BOOLEAN ST BANK OV # PKP A R
dirPhsA ENUMERATED ST 0, the code for unknown. R
phsB BOOLEAN ST BANK OV # PKP B R
dirPhsB ENUMERATED ST 0, the code for unknown. R
phsC BOOLEAN ST BANK OV # PKP C R
dirPhsC ENUMERATED ST 0, the code for unknown. R
Op ACT BANK OV # OP operands (including
individual three phases)
R
general BOOLEAN ST BANK OV # OP R
phsA BOOLEAN ST BANK OV # OP A R
phsB BOOLEAN ST BANK OV # OP B R
phsC BOOLEAN ST BANK OV # OP C R
Dpo SPS BANK OV # DPO operand R
stVal BOOLEAN ST BANK OV # DPO R
BlkRefγ ORG BANK OV # BLK setting for setting group
γ.
R
setSrcRef ObjectReference SP BANK OV # BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
OpV WYE Bank Operating Voltage in per unit for Ph
A, B, and C
R
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 Bank overvoltage # phase A
operate voltage
R
phsA.cVal Vector MX R
phsA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF CPhOvPTOV#.OpV.phsAdb R/W/C
phsA.zeroDb INT32U CF (VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
R
phsB CMV R
phsB.instCVal Vector MX R
phsB.instCVal.mag
.f
FLOAT32 Bank overvoltage # phase B
operate voltage
R
phsB.cVal Vector MX R
phsB.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsB.units Unit CF R
phsB.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF CPhOvPTOV#.OpV.phsB.db R/W/C
phsB.zeroDb INT32U CF (VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 Bank overvoltage # phase B
operate voltage
R