3-52 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.19 Directional comparison blocking (DCB_)
This element is instantiated in the following products: D60, L90.
Table 3-39: DCB data objects
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3 ORG DUTT RX3 setting. R
setSrcRef ObjectReference SP DUTT RX3 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef4 ORG DUTT RX4 setting. R
setSrcRef ObjectReference SP DUTT RX4 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DCB_PSCH1 LDevice inst: Prot UR element: Directional Comparison Blocking element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT DIR BLOCK OP operand R
general BOOLEAN ST DIR BLOCK OP R
phsA BOOLEAN ST DIR BLOCK TRIP A R
phsB BOOLEAN ST DIR BLOCK TRIP B R
phsC BOOLEAN ST DIR BLOCK TRIP C R
Tr3p ACT DIR BLOCK TRIP 3P operand R
general BOOLEAN ST DIR BLOCK TRIP 3P R
TxBlk ACT DIR BLOCK TX INIT operand R
general BOOLEAN ST DIR BLOCK TX INIT R
TxStop1 SPS DIR BLOCK TX1 STOP operand R
stVal BOOLEAN ST DIR BLOCK TX1 STOP R
TxStop2 SPS DIR BLOCK TX2 STOP operand R
stVal BOOLEAN ST DIR BLOCK TX2 STOP R
TxStop3 SPS DIR BLOCK TX3 STOP operand R
stVal BOOLEAN ST DIR BLOCK TX3 STOP R
TxStop4 SPS DIR BLOCK TX4 STOP operand R
stVal BOOLEAN ST DIR BLOCK TX4 STOP R
BlkRef1 ORG BLOCKING SCHEME BLOCK setting. R
setSrcRef ObjectReference SP BLOCKING SCHEME BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef6 ORG GND DIR O/C FWD setting. R
setSrcRef ObjectReference SP GND DIR O/C FWD reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef7 ORG GND DIR O/C REV setting. R
setSrcRef ObjectReference SP GND DIR O/C REV reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1 ORG BLOCK SCHEME RX1 setting. R
setSrcRef ObjectReference SP BLOCK SCHEME RX1 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG BLOCK SCHEME RX2 setting. R
setSrcRef ObjectReference SP BLOCK SCHEME RX2 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef3 ORG BLOCK SCHEME RX3 setting. R
setSrcRef ObjectReference SP BLOCK SCHEME RX3 reference to the data attribute to input R/C
LNName: DUTT_PSCH1 LDevice inst: Prot UR element: Direct Under-reaching Transfer Trip element