EasyManua.ls Logo

GE b30 - Page 291

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-53
3
3.5.2.20 Directional comparison blocking (DCB1_)
This element is instantiated in the following products: D60, L90.
Table 3-40: DCB1 data objects
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef4 ORG BLOCK SCHEME RX4 setting. R
setSrcRef ObjectReference SP BLOCK SCHEME RX4 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DCB1_PSCH1 LDevice inst: Prot UR element: Directional Comparison Blocking1 element
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT DIR BLOCK1 OP operand R
general BOOLEAN ST DIR BLOCK1 OP R
phsA BOOLEAN ST DIR BLOCK1 TRIP A R
phsB BOOLEAN ST DIR BLOCK1 TRIP B R
phsC BOOLEAN ST DIR BLOCK1 TRIP C R
Tr3p ACT Instantiated only on products with single
pole tripping.
R
general BOOLEAN ST DIR BLOCK1 TRIP 3P R
TxBlk ACT DIR BLOCK1 TX INIT operand R
general BOOLEAN ST DIR BLOCK1 TX INIT R
TxStop1 SPS DIR BLOCK1 TX1 STOP operand R
stVal BOOLEAN ST DIR BLOCK1 TX1 STOP R
TxStop2 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST DIR BLOCK1 TX2 STOP R
TxStop3 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST DIR BLOCK1 TX3 STOP R
TxStop4 SPS Instantiated only on products with single
pole tripping.
R
stVal BOOLEAN ST DIR BLOCK1 TX4 STOP R
BlkRef1 ORG BLOCK1 SCHEME BLOCK setting. R
setSrcRef ObjectReference SP BLOCKI1 SCHEME BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef06 ORG BLK1 SCHME DIR FWD1 setting. R
setSrcRef ObjectReference SP BLK1 SCHME DIR FWD1 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef07 ORG BLK1 SCHME DIR FWD2 setting. R
setSrcRef ObjectReference SP BLK1 SCHME DIR FWD2 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef08 ORG BLK1 SCHME DIR FWD3 setting. R
setSrcRef ObjectReference SP BLK1 SCHME DIR FWD3 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef09 ORG BLK1 SCHME DIR REV1 setting. R
setSrcRef ObjectReference SP BLK1 SCHME DIR REV1 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef10 ORG BLK1 SCHME DIR REV2 setting. R
setSrcRef ObjectReference SP BLK1 SCHME DIR REV2 reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef11 ORG BLK1 SCHME DIR REV3 setting. R
LNName: DCB_PSCH1 LDevice inst: Prot UR element: Directional Comparison Blocking element
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents

Other manuals for GE b30

Related product manuals