3-58 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
instMag.f FLOAT32 FIELD VOLTAGE R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 29, the code for volts (W/A) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF FldGnd0PHIZ1.Vol.db R/W/C
zeroDb INT32U CF 0 R
Amp MV FIELD CURRENT in amperes R
instMag AnalogueValue MX R
instMag.f FLOAT32 FIELD CURRENT R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 5, the code for amperes R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF FldGnd0PHIZ1.Amp.db R/W/C
zeroDb INT32U CF 0 R
InjVol MV INJECTED VOLTAGE in volts R
instMag AnalogueValue MX R
instMag.f FLOAT32 INJECTED VOLTAGE R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 29, the code for volts (W/A) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF FldGnd0PHIZ1.InjVol.db R/W/C
zeroDb INT32U CF 0 R
FltLocation MV FAULT LOCATION in percentage of field
winding from negative terminal in case of
single point injection. If double point
injection, displays Invalid value
R
instMag AnalogueValue MX R
instMag.f FLOAT32 FAULT LOCATION R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 1, the code for dimensionless
(percentage)
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF FldGnd0PHIZ1.FltLocation.db R/W/C
zeroDb INT32U CF 0 R
BlkRefγ ORG FIELD GROUND BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP FIELD GROUND BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: FldGnd0PHIZ1 LDevice inst: Prot UR element: FIELD GROUND INJ UC element functions
data obj. data attribute Type FC UR Name Description R/W/C