EasyManua.ls Logo

GE b30 - Page 297

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-59
3
Table 3-46: Field ground protection stage 1 objects
Table 3-47: Field ground protection stage 2 objects
3.5.2.25 Frequency rate of change (RteHz)
This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L90, N60, T60.
Table 3-48: Frequency rate of change data objects
LNName: FldGnd1PHIZ1 LDevice inst: Prot UR element: FIELD GROUND element stage 1 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FIELD GND STG1 PKP operand R
general BOOLEAN ST FIELD GND STG1 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT FIELD GND STG1 OP operand R
general BOOLEAN ST FIELD GND STG1 OP R
Dpo SPS FIELD GND STG1 DPO operand R
stVal BOOLEAN ST FIELD GND STG1 DPO R
LNName: FldGnd2PHIZ1 LDevice inst: Prot UR element: FIELD GROUND element stage 2 functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FIELD GND STG2 PKP operand R
general BOOLEAN ST FIELD GND STG2 PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT FIELD GND STG2 OP operand R
general BOOLEAN ST FIELD GND STG2 OP R
Dpo SPS FIELD GND STG2 DPO operand R
stVal BOOLEAN ST FIELD GND STG2 DPO R
LNName: RteHzPFRC# LDevice inst: Prot UR element: Frequency Rate of Change element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FREQ RATE # PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST FREQ RATE # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT FREQ RATE # OP operand R
general BOOLEAN ST FREQ RATE # OP R
Dpo SPS FREQ RATE # DPO operand R
stVal BOOLEAN ST FREQ RATE # DPO R
HzChgRte MV FREQUENCY RATE OF CHANGE # in Hz/s R
instMag AnalogueValue MX R
instMag.f FLOAT32 FREQUENCY RATE OF CHANGE # R
Mag AnalogueValue MX R
mag.f FLOAT32 FREQUENCY RATE OF CHANGE #
on deadband exception
R
units Unit CF R
units.SIUint ENUMERATED 75, the code for Rate of change of
frequency (Hz/s)
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF RteHzPFRC#.HzChgRte.db R/W/C
zeroDb INT32U CF 0 R

Table of Contents

Other manuals for GE b30

Related product manuals