3-110 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.2.76 Trip bus (TrBus)
This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60).
Table 3-125: Trip bus data objects
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 DIFF 5TH HARM Iθd magnitude,
in %
R
phsθ.instCVal.ang
.f
FLOAT32 DIFF 5TH HA UR range -180...+180 converted to 0...360R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 DIFF 5TH HARM Iθd magnitude,
in %, with deadband
R
phsθ.cVal.ang.f FLOAT32 DIFF 5TH HA UR range -180...+180 converted to 0...360R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 1, the code for dimensionless R
phsθ.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsθ.db INT32U CF PctDifPDIF#.DifA5thH.phsθ.db R/W/C
phsθ.dbAng INT32U CF PctDifPDIF#.DifA5thH.phsθ.dbAn
g
R/W/C
phsθ.zeroDb INT32U CF 0 R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
RstA WYE Phase restraint currents R
phsθ CMV R
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 REST PHASOR Iθr magnitude, in
pu
R
phsθ.instCVal.ang
.f
FLOAT32 REST PHASOR UR range -180...+180 converted to 0...360R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 REST PHASOR Iθr magnitude, in
pu, with deadband
R
phsθ.cVal.ang.f FLOAT32 REST PHASOR UR range -180...+180 converted to 0...360R
phsθ
.units Unit CF R
phsθ.units.SIUnit ENUMERATED 1, the code for dimensionless R
phsθ.units
.multiplier
ENUMERATED -2, the code for a multiplier of Centi R
phsθ.db INT32U CF PctDifPDIF#.RstA.phsθ.db R/W/C
phsθ.dbAng INT32U CF PctDifPDIF#.RstA.phsθ.dbAng R/W/C
phsθ.zeroDb INT32U CF 0 R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
BlkRefγ ORG PERCENT DIFF BLOCK for setting group γ.R
setSrcRef ObjectReference SP PERCENT DIFF BLOCK for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: TrBusPTRC# LDevice inst: Prot UR element: Trip Bus element #
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT TRIP BUS # OP operand, which becomes
On when any input is On, and the element
is not blocked
R
general BOOLEAN ST TRIP BUS # OP R
Str ACD TRIP BUS # PKP operand, which indicates
Op will operate when delay expires.
R
general BOOLEAN ST TRIP BUS # PKP R
LNName: PctDifPDIF1 LDevice inst: Prot UR element: Transformer Percent Differential function
data obj. data attribute Type FC UR Name Description R/W/C