CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-111
3
3.5.2.77 Trip output (TrOut)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-126: Trip output data objects
dirGeneral ENUMERATED ST 0, the code for unknown R
InRefαα ORG TRIP BUS # INPUT α setting. R
setSrcRef ObjectReference SP TRIP BUS # INPUT α setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef99 ORG TRIP BUS # RESET setting, which when On
resets the non-volatile set-dominant
input conditions latch.
R
setSrcRef ObjectReference SP TRIP BUS # RESET setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG TRIP BUS # BLOCK setting. R
setSrcRef ObjectReference SP TRIP BUS # BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: TrOutPTRC1 LDevice inst: Prot UR element: Trip Output element
data obj. data attribute Type FC UR Name Description R/W/C
Tr ACT TRIP OUTPUT OP (any trip) operand R
general BOOLEAN ST TRIP OUTPUT OP R
Tr3p ACT TRIP 3-POLE operand R
general BOOLEAN ST TRIP 3-POLE R
Tr1p ACT general is TRIP 1-POLE operand, phsA is
TRIP PHASE A operand, phsB is TRIP
PHASE B operand and phsC is TRIP PHASE
C operand
R
general BOOLEAN ST TRIP 1-POLE R
phsA BOOLEAN ST TRIP PHASE A R
phsB BOOLEAN ST TRIP PHASE B R
phsC BOOLEAN ST TRIP PHASE C R
StrRec3p SPS TRIP AR INIT 3-POLE operand R
stVal BOOLEAN ST TRIP AR INIT 3-POLE R
Tr3pFrcd SPS TRIP FORCE 3-POLE operand (3-pole trip
mode is being forced)
R
stVal BOOLEAN ST TRIP FORCE 3-POLE R
StrZ2PhDl SPS TRIP Z2PH TMR INIT operand R
stVal BOOLEAN ST TRIP Z2PH TMR INIT R
StrZ2GndDl SPS TRIP Z2GR TMR INIT operand R
stVal BOOLEAN ST TRIP Z2GR TMR INIT R
InRef3α ORG TRIP 3-POLE INPUT-α setting. R
setSrcRef ObjectReference SP TRIP 3-POLE INPUT-α setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef1α ORG TRIP 1-POLE INPUT-α setting. R
setSrcRef ObjectReference SP TRIP 1-POLE INPUT-α setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2α ORG TRIP RECLOSE INPUT-α setting. R
setSrcRef ObjectReference SP TRIP RECLOSE INPUT-α setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef01 ORG START TMR Z2PH Inp1 setting. R
setSrcRef ObjectReference SP START TMR Z2PH Inp1 setting reference to the data attribute to input R/C
LNName: TrBusPTRC# LDevice inst: Prot UR element: Trip Bus element #
data obj. data attribute Type FC UR Name Description R/W/C