CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-119
3
Table 3-140: Breaker arcing current phase data objects
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRef1 ORG BKR # ARC AMP BLOCK setting R
setSrcRef ObjectReference SP BKR # ARC AMP BLOCK reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
ColOpn SPS Logical OR of status value of mapped
FlexLogic operands in BKR # ARC AMP
INT- A, BKR # ARC AMP INT- B, BKR # ARC
AMP INT- C
R
stVal BOOLEAN ST Logical OR condition to
CBArc1SCBR#.ColOpn,
CBArc2SCBR#.ColOpn,
CBArc3SCBR#.ColOpn
R
OpTmOpn MV BKR # OPERATING TIME in ms R
instMag AnalogueValue MX R
instMag.f FLOAT32 Mapped BKR # OPERATING TIME R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
units.SIUnit ENUMERATED 4, the code for Time (Sec) R
units.multiplier ENUMERATED -3, the code for a multiplier of 1/1000 R
db INT32 CF CBArc0SCBR#.OpTmOpn.db R/W/C
zeroDb INT32 CF 0 R
MemClr SPC CLEAR BREAKER # ARCING AMPS
command
R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF CBArc0SCBR#.MemClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
LNName: CBArcΘSCBR# LDevice inst: Ctrl UR element: BREAKER # ARCING CURRENT element
data obj. data attribute Type FC UR Name Description R/W/C
ColOpn SPS Status value of mapped FlexLogic
operand in BKR # ARC AMP INT- ψ
R
stVal BOOLEAN ST Status value of mapped
FlexLogic operand in BKR # ARC
AMP INT- ψ setting
R
InRef1 ORG BKR # ARC AMP INT-µ setting R
setSrcRef ObjectReference SP BKR # ARC AMP INT- µ reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
AccAbr MV BKR # ACC ARCING AMP ψ in A2s R
instMag AnalogueValue MX R
instMag.f FLOAT32 BKR # ACC ARCING AMP ψ R
mag Analogue Value MX R
mag.f FLOAT32 instMag.f on deadband
exception
R
units Unit CF R
LNName: CBArc0SCBR# LDevice inst: Ctrl UR element: BREAKER # ARCING CURRENT element
data obj. data attribute Type FC UR Name Description R/W/C