CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-129
3
3.5.3.14 Fault location (FltRpt)
This element is instantiated in the following products: C60, D30, D60, F35, F60, L30, L60, L90.
Table 3-149: Fault report settings data objects
zeroDb INT32U CF 0 R
InRef1 ORG DIGITIZER # SOURCE setting. R
setSrcRef ObjectReference SP DIGITIZER # SOURCE setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: FltRptRFLO#LDevice inst: CtrlUR element: FAULT REPORT # settings
data obj. data attribute Type FC UR Name Description R/W/C
TapLocFlt SPS TAP-LOCAL FAULT operand R
stVal BOOLEAN ST TAP-LOCAL FAULT R
NumRcd
INS
Actual number of records
R
stVal INT32 ST
Modbus register 3020h, I.e.,
“Number of Fault Reports”
R
FltZ CMV Mandatory data attribute which in this
case is fixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 0 R
cVal.ang.f FLOAT32 0 R
RsStat SPC instantiated only in FltRptRFLO1 R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDurINT32U 2 ms (actually one pass) R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF
FltRptRFLO1.RsStat
.ctlModel R/W/C
sboT
imeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operT
imeout INT32U CF 0 R
InRef1 ORG FAULT REPORT# TRIG. R
setSrcRef ObjectReference SP FAULT REPORT# TRIG. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
InRef2 ORG Only instantiated in FltRptRFLO1 R
setSrcRef ObjectReference SP CLEAR FAULT REPORTS. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: DgtzrGAPC# LDevice inst: Ctrl UR element: Digitizer #
data obj. data attribute Type FC UR Name Description R/W/C