3-130 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-150: Fault report data file data objects
3.5.3.15 Frequency out-of-band accumulation (HzBnd)
This element is instantiated in the following products: G30, G60.
Table 3-151: Frequency out-of-band accumulation data objects
Table 3-152: Frequency out-of-band accumulation prefix instance number $ data objects
LNName: FltRFLOψψLDevice inst: CtrlUR element: Selected values from Fault Report Data
f
ile ψψ
data obj. data attribute Type FC UR Name Description R/W/C
FltZ CMV Mandatory data attribute which in this
case is f ixed at zero
R
cVal Vector MX R
cVal.mag.f FLOAT32 Fault impedance magnitude in
primary ohms calculated as
shown below
R
cVal.ang.f FLOAT32 Fault impedance angle in
degrees calculated as shown
below
R
FltRis MV FAULTψψ FAULT RESIST converted to
primary ohms
R
mag AnalogueValue MX R
mag.f FLOAT32 Actual Value FAULTψψ FAULT
RESIST converted to primary
ohms
R
units Unit CF R
units.SIUnit ENUMERATED 30, the code for primary electric
resistance in ohm (V/A)
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
FltLoopRis MV FAULTψψ LOOP RESIST converted to
primary ohms
R
mag AnalogueValue MX R
LNName: HzBndPTUF1 LDevice inst: Ctrl UR element: Frequency OOB Accumulation element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FREQ OOB ACCUM PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST FREQ OOB ACCUM PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT FREQ OOB ACCUM OP operand R
general BOOLEAN ST FREQ OOB ACCUM OP R
BlkRef1 ORG FREQ ACCUM BLOCK setting. R
setSrcRef ObjectReference SP FREQ ACCUM BLOCK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: HzBnd$PTUF1 LDevice inst: Ctrl UR element: Frequency OOB Accumulator $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD FREQ OOB BAND $ PKP operand, which is
indicates Op will operate when delay
expires.
R
general BOOLEAN ST FREQ OOB BAND $ PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. R
Op ACT FREQ OOB BAND $ OP operand R
general BOOLEAN ST FREQ OOB BAND $ OP R
Dpo SPS FREQ OOB BAND $ DPO operand R
stVal BOOLEAN ST FREQ OOB BAND $ DPO R
HzObAccu
m
MV FREQUENCY OOB BAND $
ACCUMULATION in percentage (%)
R