3-134 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.3.18 Maximum starting rate (StrRte)
This element is instantiated in the following products: M60.
Table 3-155: Maximum starting rate data objects
phsB BOOLEAN ST INCIPNT FLT # OP B R
phsC BOOLEAN ST INCIPNT FLT # OP C R
FltCntPhφ INS INCIPIENT FAULT # PH θ FAULTS R
stVal INT32 ST INCIPIENT FAULT # PH θ FAULTS R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
FltCntClr SPC Only instantiated in ICFltPTEF1 R/Ctrl
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF ICFltPTEF#.FltCntClr.ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
BlkRef1 ORG INCIPNT FLT # BLOCK setting R
GEORG R
setSrcRef ObjectReference SP INCIPNT FLT # BLOCK. reference to the data attribute to input R/C
VISIBLE
STRING255
SP Reference to the ultimate source
of value selected by setting
INCIPNT FLT # BLOCK.
R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: StrRtePMRI1 LDevice inst: Ctrl UR element: Maximum starting rate element
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD STARTS-PER-HOUR PKP operand R
general BOOLEAN ST STARTS-PER-HOUR PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT STARTS-PER-HOUR OP operand R
general BOOLEAN ST STARTS-PER-HOUR OP R
Dpo SPS STARTS-PER-HOUR DPO operand, which
is the inverse of STARTS-PER-HOUR PKP
R
LNName: ICFltPTEF# LDevice inst: Ctrl UR element: Incipient Cable Fault Element #
data obj. data attribute Type FC UR Name Description R/W/C