CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-163
3
TagOn SPS SWITCH # TAG ON operand R
stVal BOOLEAN ST SWITCH # TAG ON R
TagOff SPS SWITCH # TAG OFF operand R
stVal BOOLEAN ST SWITCH # TAG OFF R
SbstCls SPS SWITCH # SUBD CLSD operand R
stVal BOOLEAN ST SWITCH # SUBD CLSD R
SbstOpn SPS SWITCH # SUBD OPEN operand R
stVal BOOLEAN ST SWITCH # SUBD OPEN R
BypsOn SPS SWITCH # BYPASS ON operand R
stVal BOOLEAN ST SWITCH # BYPASS ON R
BypsOff SPS SWITCH # BYPASS OFF operand R
stVal BOOLEAN ST SWITCH # BYPASS OFF R
Pos DPC Disconnect switch position control R/Ctrl
stVal CODED ENUM ST R
stSeld BOOLEAN ST The controllable data status is “selected” R
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 0 (pulse) R
pulseConfig.onDur INT32U 2 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 1 R
ctlModel CtlModels CF XSWI# Pos ctlModel R/W/C
sboTimeout INT32U CF XSWI# Pos sboTimeout R/W/C
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF SWITCH # Toperate R/C
BlkOpn SPC Blocks disconnect switch open
commands from all sources including
protection
R/Ctrl
stVal BOOLEAN ST R
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 1 (persistent) R
pulseConfig.onDur INT32U 0 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 0 R
ctlModel CtlModels CF Disc0XSWI# BlkOpn ctlModel R/W/C
sboTimeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
operTimeout INT32U CF 0 R
BlkCls SPC Blocks disconnect switch close
commands from all sources
R/Ctrl
stVal BOOLEAN ST R
pulseConfig PulseConfig CF R
pulseConfig
.cmdQual
ENUMERATED 1 (persistent) R
pulseConfig.onDur INT32U 0 R
pulseConfig
.offDur
INT32U 0 R
pulseConfig
.numPls
INT32U 0 R
ctlModel CtlModels CF Disc0XSWI# BlkCls ctlModel R/W/C
sboTimeout INT32U CF 30000 R
LNName: Disc0XSWI# LDevice inst: System UR element: Disconnect Control element #
data obj. data attribute Type FC UR Name Description R/W/C