3-162 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-179: Disconnect switch Disc0XSWI data objects
VISIBLE
STRING255
SP If reference is external to this
IED, mapped to the source’s
GOOSE control block, else empty
string
R/C
cdcNs VISIBLE
STRING255
EX Name of the GE Multilin
namespace at the time of this
firmware release
R
cdcName VISIBLE
STRING255
EX GEORG R
LNName: Disc0XSWI# LDevice inst: System UR element: Disconnect Control element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
EEHealth ENS Disconnect switch health, value is 3 (red)
when disconnect switch trouble is
detected
R
INS R
stVal ENUMERATED ST 3 when operand SWITCH # TROUBLE is
On, otherwise 1
R
Loc SPS Value of operand selected by XSWI#
ST.LOC OPERAND
R
stVal BOOLEAN ST Value of operand selected by setting
XSWI# ST.LOC OPERAND
R
OpCnt INS Disconnect switch operations counter. R
stVal INT32 ST R
units Unit CF R
units.SIUnit ENUMERATED 1 R
units.multiplier ENUMERATED 0 R
SwTyp ENS Disconnect switch type, fixed at 2
(Disconnector)
R
INS R
stVal ENUMERATED ST 2 R
SwOpCap INS Mandatory data object which in this case
is fixed at 4
R
stVal ENUMERATED ST 4 R
OpOpn ACT SWITCH # OFF CMD (open) operand R
general BOOLEAN ST SWITCH # OFF CMD R
OpCls ACT SWITCH # ON CMD (close) operand R
general BOOLEAN ST SWITCH # ON CMD R
BadSt1 SPS SWITCH # BAD STATUS operand R
stVal BOOLEAN ST SWITCH # BAD STATUS R
ClsSt1 SPS SWITCH # CLOSED operand R
stVal BOOLEAN ST SWITCH # CLOSED R
OpnSt1 SPS SWITCH # OPEN operand R
stVal BOOLEAN ST SWITCH # OPEN R
Dsc SPS SWITCH # DISCREP operand, which is
disconnect pole discrepancy status
R
stVal BOOLEAN ST SWITCH # DISCREP R
Alm SPS SWITCH # TROUBLE operand, which is
disconnect pole discrepancy, bad-status,
or SWITCH # EXT ALARM
R
stVal BOOLEAN ST SWITCH # TROUBLE R
LNName: DiscCILO# LDevice inst: System UR element: Disconnect Control element #
data obj. data attribute Type FC UR Name Description R/W/C