CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-175
3
phsBC.instCVal
.mag.f
FLOAT32 SRC # Phase BC Voltage
Magnitude
R
phsBC.instCVal
.ang.f
FLOAT32 SRC # Phase BC Voltage Angle UR range -180...+180 converted to 0...360R
phsBC.cVal Vector MX R
phsBC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsBC.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsBC.units Unit CF R
phsBC.units
.SIUnit
ENUMERATED 29, the code for primary volts (W/A) R
phsBC.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsBC.db INT32U CF MMXU# PPV.phsBC.db R/W/C
phsBC.dbAng INT32U CF MMXU# PPV.phsBC.dbAng R/W/C
phsBC.zeroDb INT32U CF voltage cut-off level. R
phsCA CMV R
phsCA.instCVal Vector MX R
phsCA.instCVal
.mag.f
FLOAT32 SRC # Phase CA Voltage
Magnitude
R
phsCA.instCVal
.ang.f
FLOAT32 SRC # Phase CA Voltage Angle UR range -180...+180 converted to 0...360R
phsCA.cVal Vector MX R
phsCA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsCA.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsCA.units Unit CF R
phsCA.units
.SIUnit
ENUMERATED 29, the code for primary volts (W/A) R
phsCA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsCA.db INT32U CF MMXU# PPV.phsCA .db R/W/C
phsCA.dbAng INT32U CF MMXU# PPV.phsCA.dbAng R/W/C
phsCA.zeroDb INT32U CF voltage cut-off level. R
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
VabRMS MV SRC # Phase AB Voltage RMS, in primary
volts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase AB Voltage RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 29, the code for primary volts (W/A) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS PPV.phsAB
DEADBAND
R/W/C
zeroDb INT32U CF voltage cut-off level. R
VbcRMS MV SRC # Phase BC Voltage RMS, in primary
volts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase BC Voltage RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 29, the code for primary volts (W/A) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS PPV.phsBC
DEADBAND
R/W/C
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C