3-176 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
zeroDb INT32U CF voltage cut-off level. R
VcaRMS MV SRC # Phase CA Voltage RMS, in primary
volts
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # Phase CA Voltage RMS R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 29, the code for primary volts (W/A) R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF MMXU# RMS PPV.phsCA
DEADBAND
R/W/C
zeroDb INT32U CF voltage cut-off level. R
PhV WYE SRC # Phase Voltage phasors, in primary
volts
R
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 SRC # Phase AG Voltage
Magnitude
R
phsA.instCVal.ang
.f
FLOAT32 SRC # Phase AG Voltage Angle UR range -180...+180 converted to 0...360R
phsA.cVal Vector MX R
phsA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsA.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 29, the code for primary volts (W/A) R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF MMXU# PhV.phsA.db R/W/C
phsA.dbAng INT32U CF MMXU# PhV.phsA .dbAng R/W/C
phsA.zeroDb INT32U CF voltage cut-off level. R
phsB CMV R
phsB.instCVal Vector MX R
phsB.instCVal.mag
.f
FLOAT32 SRC # Phase BG Voltage
Magnitude
R
phsB.instCVal.ang
.f
FLOAT32 SRC # Phase BG Voltage Angle UR range -180...+180 converted to 0...360R
phsB.cVal Vector MX R
phsB.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsB.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
phsB.units Unit CF R
phsB.units.SIUnit ENUMERATED 29, the code for primary volts (W/A) R
phsB.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsB.db INT32U CF MMXU# PhV.phsB .db R/W/C
phsB.dbAng INT32U CF MMXU# PhV.phsB.dbAng R/W/C
phsB.zeroDb INT32U CF voltage cut-off level. R
phsC CMV R
phsC.instCVal Vector MX R
phsC.instCVal.mag
.f
FLOAT32 SRC # Phase CG Voltage
Magnitude
R
phsC.instCVal.ang
.f
FLOAT32 SRC # Phase CG Voltage Angle UR range -180...+180 converted to 0...360R
phsC.cVal Vector MX R
phsC.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsC.cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
LNName: ACsrcMMXU# LDevice inst: Meter UR element: AC Source #
data obj. data attribute Type FC UR Name Description R/W/C

Table of Contents