3-188 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # DMD W R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 38 is unit for power in watts R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF DmdMtrMMTR#.WDmd.db R/W/C
zeroDb INT32U CF power cut-off level. R
WMaxDmd
Dt
MV SRC # DMD W, in primary watt, with
associated date, SRC # DMD W DATE
R
mag AnalogueValue MX R
mag.f FLOAT32 SRC # DMD W MAX R
units Unit CF R
units.SIUnit ENUMERATED 38 is unit for power in watts R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
VArDmd MV SRC # DMD VAR, in primary volt ampere
reactive
R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # DMD VAR R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 63 is unit for apparent power in volt-
ampere
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF DmdMtrMMTR#.VArDmd.db R/W/C
zeroDb INT32U CF power cut-off level. R
VArMaxDm
dDt
MV SRC # DMD VAR, in primary volt ampere
reactive, with associated date, SRC #
DMD VAR DATE
R
mag AnalogueValue MX R
mag.f FLOAT32 SRC # DMD VAR MAX R
units Unit CF R
units.SIUnit ENUMERATED 63 is unit for apparent power in volt-
ampere
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
VADmd MV SRC # DMD VA, in primary volt ampere R
instMag AnalogueValue MX R
instMag.f FLOAT32 SRC # DMD VA R
mag AnalogueValue MX R
mag.f FLOAT32 instMag.f deadbanded R
units Unit CF R
units.SIUnit ENUMERATED 61 is unit for apparent power in volt-
ampere
R
units.multiplier ENUMERATED 0, the code for a multiplier of 1 R
db INT32U CF DmdMtrMMTR#.VADmd.db R/W/C
zeroDb INT32U CF power cut-off level. R
VAMaxDm
dDt
MV SRC # DMD VA, in primary volt ampere,
with associated date, SRC # DMD VA
DATE
R
mag AnalogueValue MX R
mag.f FLOAT32 SRC # DMD VA MAX R
units Unit CF R
LNName: DmdMtrMMTR# LDevice inst: Meter UR element: Signal Source # NAME Demand Metering
data obj. data attribute Type FC UR Name Description R/W/C