2-46 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 3034 Fault Report 3 Time 0 to 4294967295 --- 1 F050 0
" 3036 Fault Report 4 Time 0 to 4294967295 --- 1 F050 0
" 3038 Fault Report 5 Time 0 to 4294967295 --- 1 F050 0
" 303A Fault Report 6 Time 0 to 4294967295 --- 1 F050 0
" 303C Fault Report 7 Time 0 to 4294967295 --- 1 F050 0
" 303E Fault Report 8 Time 0 to 4294967295 --- 1 F050 0
" 3040 Fault Report 9 Time 0 to 4294967295 --- 1 F050 0
" 3042 Fault Report 10 Time 0 to 4294967295 --- 1 F050 0
" 3044 Fault Report 11 Time 0 to 4294967295 --- 1 F050 0
" 3046 Fault Report 12 Time 0 to 4294967295 --- 1 F050 0
" 3048 Fault Report 13 Time 0 to 4294967295 --- 1 F050 0
" 304A Fault Report 14 Time 0 to 4294967295 --- 1 F050 0
" 304C Fault Report 15 Time 0 to 4294967295 --- 1 F050 0
User Programmable Fault Report Commands (Read/Write Command)
B30, B90, C70,
G30, G60, M60,
N60, T35, T60
3060 User Fault Report Clear 0 to 1 --- 1 F126 0 (No)
User Programmable Fault Report Actual Values (Read Only)
B30, B90, C70,
G30, G60, M60,
N60, T35, T60
3070 Newest Record Number 0 to 65535 --- 1 F001 0
" 3071 Cleared Date 0 to 4294967295 --- 1 F050 0
" 3073 Report Date (10 items) 0 to 4294967295 --- 1 F050 0
User Programmable Fault Report (Read/Write Setting) (2 Modules)
B30, B90, C70,
G30, G60, M60,
N60, T35, T60
3090 Fault Report 1 Fault Trigger 0 to 4294967295 --- 1 F300 0
" 3092 Fault Report 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 3093 Fault Report 1 Prefault Trigger 0 to 4294967295 --- 1 F300 0
" 3095 Fault Report Analog Channel 1 (32 items) 0 to 65536 --- 1 F600 0
" 30B5 Fault Report 1 Reserved (5 items) --- --- --- F001 0
" 30BA ...Repeated for Fault Report 2
Modbus File Transfer (Read/Write)
All 3100 Name of File to Read --- --- --- F204 (none)
Modbus File Transfer Values (Read Only)
All 3200 Character Position of Current Block within
File
0 to 4294967295 --- 1 F003 0
" 3202 Size of Currently-available Data Block 0 to 65535 --- 1 F001 0
" 3203 Block of Data from Requested File (122
items)
0 to 65535 --- 1 F001 0
Security (Read/Write Setting)
All 3280 Administrator Alphanumeric Password
Setting
--- --- --- F202 (none)
Security (Read Only)
All 328A Administrator Alphanumeric Password
Status
0 to 1 --- 1 F102 0 (Disabled)
Security (Read/Write)
All 328B Administrator Alphanumeric Password
Entry
--- --- --- F202 (none)
Products Address Register name Range Units Step Format Default