CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-47
2
Security (Read/Write Setting)
All 3295 Supervisor Alphanumeric Password Setting --- --- --- F202 (none)
Security (Read Only)
All 329F Supervisor Alphanumeric Password Status 0 to 1 --- 1 F102 0 (Disabled)
Security (Read/Write)
All 32A0 Supervisor Alphanumeric Password Entry --- --- --- F202 (none)
Security (Read/Write Setting)
All 32AA Engineer Alphanumeric Password Setting --- --- --- F202 (none)
Security (Read Only)
All 32B4 Engineer Alphanumeric Password Status 0 to 1 --- 1 F102 0 (Disabled)
Security (Read/Write)
All 32B5 Engineer Alphanumeric Password Entry --- --- --- F202 (none)
Security (Read/Write Setting)
All 32BF Operator Alphanumeric Password Setting --- --- --- F202 (none)
Security (Read Only)
All 32C9 Operator Alphanumeric Password Status 0 to 1 --- 1 F102 0 (Disabled)
Security (Read/Write)
All 32CA Operator Alphanumeric Password Entry --- --- --- F202 (none)
Security (Read/Write Setting)
All 32D4 Observer Alphanumeric Password Setting --- --- --- F202 (none)
Security (Read Only)
All 32DE Observer Alphanumeric Password Status 0 to 1 --- 1 F102 0 (Disabled)
Security (Read/Write)
All 32DF Observer Alphanumeric Password Entry --- --- 1 F202 (none)
Security (Read Only)
All 32E9 Reserved for password settings of future
roles (63 items)
0 to 65535 --- 1 F001 0
" 3328 Security Status Indicator 0 to 65535 --- 1 F618 0
Security (Read/Write Setting)
All 3329 Session Lockout 0 to 99 --- 1 F001 3
" 332A Session Lockout Period 0 to 9999 min 1 F001 3
" 332B Load Factory Defaults 0 to 1 --- 1 F126 0 (No)
" 332C Syslog Server IP Address 0 to 4294967295 --- 1 F003 0
" 332E Syslog Server Port Number 1 to 65535 --- 1 F001 514
Security Supervisory (Read/Write Setting)
All 3331 Device Authentication Enable 0 to 1 --- 1 F126 1 (Yes)
" 3332 Supervisor Role Enable 0 to 1 --- 1 F102 0 (Disabled)
" 3333 Lock Relay 0 to 1 --- 1 F102 0 (Disabled)
" 3334 Factory Service Mode Enable 0 to 1 --- 1 F102 0 (Disabled)
" 3335 Failed Authentication Alarm Enable 0 to 1 --- 1 F102 1 (Enabled)
" 3336 Firmware Lock Alarm 0 to 1 --- 1 F102 1 (Enabled)
" 3337 Settings Lock Alarm 0 to 1 --- 1 F102 1 (Enabled)
" 3338 Bypass Access 0 to 4 --- 1 F628 0 (Disabled)
" 333A Serial Inactivity Timeout 1 to 9999 min 1 F001 1
Security Command (Read/Write Command)
All 3350 Operator Logoff 0 to 1 --- 1 F126 0 (No)
" 3351 Engineer Logoff 0 to 1 --- 1 F126 0 (No)
Products Address Register name Range Units Step Format Default