EasyManuals Logo

GE b30 Communications Guide

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
2-66 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Transformer General (Read/Write Setting)
G30, T35, T60 4630 Transformer Number of Windings 2 to 6 --- 1 F001 2
" 4631 Transformer Phase Compensation 0 to 1 --- 1 F160 0 (Internal
(software))
" 4632 Transformer Load Loss at Rated Load 1 to 20000 kW 1 F001 100
" 4633 Transformer Rated Winding Temperature
Rise
0 to 4 --- 1 F161 1 (65°C (oil))
" 4634 Transformer No Load Loss 1 to 20000 kW 1 F001 10
" 4635 Transformer Type of Cooling 0 to 6 --- 1 F162 0 (OA)
" 4636 Transformer Top-oil Rise Over Ambient 1 to 200 °C 1 F001 35
" 4637 Transformer Thermal Capacity 0 to 200 kWh/°C 0.01 F001 10000
" 4638 Transformer Winding Thermal Time
Constant
0.25 to 15 min 0.01 F001 200
" 4639 Transformer Reference Winding Manual
Selection
0 to 7 --- 1 F470 0
(Auto. Selecti
on)
Transformer Windings (Read/Write Settings) (2 or 6 Modules)
G30, T35, T60 4640 Transformer Winding 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 4641 Transformer Winding 1 Rated MVA 0.001 to 2000 MVA 0.001 F003 100000
" 4643 Transformer Winding 1 Nominal Phase-
Phase Voltage
0.001 to 2000 kV 0.001 F003 220000
" 4645 Transformer Winding 1 Connection 0 to 2 --- 1 F163 0 (Wye)
" 4646 Transformer Winding 1 Grounding 0 to 1 --- 1 F164 0 (Not within
zone)
" 4647 Transformer Winding 1 Angle w.r.t. Winding
1
-359.9 to 0 degrees 0.1 F002 0
" 4651 Transformer Winding 1 Resistance 0.0001 to 100 ohms 0.000
1
F003 100000
" 4653 ...Repeated for Transformer Winding 2
T35, T60 4666 ...Repeated for Transformer Winding 3
" 4679 ...Repeated for Transformer Winding 4
" 468C ...Repeated for Transformer Winding 5
" 469F ...Repeated for Transformer Winding 6
Incipient Cable Fault Detector (Read/Write Settings) (1, 2, or 6 Modules)
D30, F35, F60,
L30
46B2 Incipient Cable Fault Detector 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 46B3 Incipient Cable Fault Detector 1 Block 0 to 4294967295 --- 1 F300 0
" 46B5 Incipient Cable Fault Detector 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 46B6 Incipient Cable Fault Detector 1 Pickup 0.1 to 10 pu 0.01 F001 50
" 46B7 Incipient Cable Fault Detector 1 Mode 0 to 1 --- 1 F254 0 (Number of
Counts)
" 46B8 Incipient Cable Fault Detector 1 Counts 1 to 10 --- 1 F001 2
" 46B9 Incipient Cable Fault Detector 1 Time
Window
0 to 1000 s 0.01 F003 1000
" 46BB Incipient Cable Fault Detector 1 Reset
Delay
0 to 65.535 s 0.001 F001 100
" 46BC Incipient Cable Fault Detector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 46BD Incipient Cable Fault Detector 1 Events 0 to 1 --- 1 F102 0 (Disabled)
F35, F60 46BE ...Repeated for Incipient Cable Fault
Detector 2
F35 46CA ...Repeated for Incipient Cable Fault
Detector 3
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals