CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-73
2
Neutral Time Overcurrent (Read/Write Grouped Setting) (2, 4, or 6 Modules)
B30, C60, C70,
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
M60, N60, T60
5B00 Neutral Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
" 5B02 Neutral Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
" 5B03 Neutral Time Overcurrent 1 Pickup 0.02 to 30 pu 0.001 F001 1000
" 5B04 Neutral Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod
Inv)
" 5B05 Neutral Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
" 5B06 Neutral Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0
(Instantaneo
us)
" 5B07 Neutral Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 5B09 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 5B0A Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 5B0B Reserved (6 items) 0 to 1 --- 1 F001 0
" 5B11 ...Repeated for Neutral Time Overcurrent 2
B30, C60, C70,
D60, F35, F60,
L30, L60, L90,
M60, N60, T60
5B22 ...Repeated for Neutral Time Overcurrent 3
B30, C60, C70,
D60, F35, F60,
L30, L60, L90,
M60, N60, T60
5B33 ...Repeated for Neutral Time Overcurrent 4
B30, C60, C70,
F35, F60, L90,
M60, N60, T60
5B44 ...Repeated for Neutral Time Overcurrent 5
" 5B55 ...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting)
(1, 2, 4, 6, 8, or 12 Modules)
All except B90,
C30, T35
5C00 Neutral Instantaneous Overcurrent 1
Function
0 to 1 --- 1 F102 0 (Disabled)
" 5C01 Neutral Instantaneous Overcurrent 1 Signal
Source
0 to 5 --- 1 F167 0 (SRC 1)
" 5C02 Neutral Instantaneous Overcurrent 1
Pickup
0.02 to 30 pu 0.001 F001 1000
" 5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
" 5C04 Neutral Instantaneous Overcurrent 1 Reset
Delay
0 to 600 s 0.01 F001 0
" 5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 5C07 Neutral Instantaneous Overcurrent 1
Target
0 to 2 --- 1 F109 0 (Self-reset)
" 5C08 Neutral Instantaneous Overcurrent 1
Events
0 to 1 --- 1 F102 0 (Disabled)
" 5C09 Reserved (8 items) 0 to 1 --- 1 F001 0
B30, C60, C70,
D30, D60, F35,
F60, L30, L60,
L90, M60, N60,
T60
5C11 ...Repeated for Neutral Instantaneous
Overcurrent 2
Products Address Register name Range Units Step Format Default