GE Multilin D60 Line Distance Protection System 4-31
4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE
4
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic operand is set to “On” and the
D60 does not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
REMOTE ACCESS DENIED FlexLogic operand is set to “Off” after the expiration of the ten-minute timeout.