GE Multilin D60 Line Distance Protection System 5-77
5 SETTINGS 5.2 PRODUCT SETUP
5
See the LED Indicators section in chapter 4 for information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
LED 1 TYPE setting is “Self-
Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the
LED 1 TYPE setting is
“Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communica-
tions channel, or from any programmed operand, even if the LED operand state de-asserts.
See the figure in the Setting Groups section in the Control Elements section later in this chapter for an example of group
activation.
5.2.11 USER-PROGRAMMABLE SELF-TESTS
For user-programmable self-tests for CyberSentry, use the Setup > Security > Supervisory menu instead.
PATH: SETTINGS PRODUCT SETUP  USER-PROGRAMMABLE SELF TESTS
Table 5–10: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING PARAMETER SETTING PARAMETER
LED 1 operand SETTING GROUP ACT 1 LED 13 operand Off
LED 2 operand SETTING GROUP ACT 2 LED 14 operand BREAKER 2 OPEN
LED 3 operand SETTING GROUP ACT 3 LED 15 operand BREAKER 2 CLOSED
LED 4 operand SETTING GROUP ACT 4 LED 16 operand BREAKER 2 TROUBLE
LED 5 operand SETTING GROUP ACT 5 LED 17 operand SYNC 1 SYNC OP
LED 6 operand SETTING GROUP ACT 6 LED 18 operand SYNC 2 SYNC OP
LED 7 operand Off LED 19 operand Off
LED 8 operand Off LED 20 operand Off
LED 9 operand BREAKER 1 OPEN LED 21 operand AR ENABLED
LED 10 operand BREAKER 1 CLOSED LED 22 operand AR DISABLED
LED 11 operand BREAKER 1 TROUBLE LED 23 operand AR RIP
LED 12 operand Off LED 24 operand AR LO
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.