EasyManuals Logo

GE D60 User Manual

GE D60
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
1-20 D60 Line Distance Protection System GE Multilin
1.5 USING THE RELAY 1 GETTING STARTED
1
1.5.7 COMMISSIONING
The D60 requires minimal maintenance after it is commissioned into service. Since the D60 is a microprocessor-based
relay, its characteristics do not change over time. As such, no further functional tests are required.
The D60 performs a number of continual self-tests and takes the necessary action in case of any major errors (see the
Relay Self-tests section in chapter 7). However, it is recommended that D60 maintenance be scheduled with other system
maintenance. This maintenance can involve in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1. Visual verification of the analog values integrity, such as voltage and current (in comparison to other devices on the
corresponding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.
Out-of-service maintenance:
1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.
Unscheduled maintenance, such as a disturbance causing system interruption:
1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for service.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D60 and is the answer not in the manual?

GE D60 Specifications

General IconGeneral
Frequency50/60 Hz
ManufacturerGeneral Electric (GE)
Communication ProtocolsDNP3
MountingPanel mount
Operating Temperature-20°C to +60°C

Related product manuals