GE Multilin D60 Line Distance Protection System 5-123
5 SETTINGS 5.4 SYSTEM SETUP
5
MODIFICATION OF SYNC WORD IN CFG-2 FOR TR 90-5 DATA SETS
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets).  In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word, which should presently be set to 2) is set as follows:
The PMU settings are organized in logical groups as follows.
PATH: SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1
VALUE 
(DECIMAL) 
 
# OF ASDUS
 11  1
 12  2
 13  3
 14  4
 PHASOR MEASUREMENT
 UNIT 1
 PMU 1 BASIC
 CONFIGURATION
See page 5-124.
MESSAGE
 PMU 1
 CALIBRATION
See page 5–128.
MESSAGE
 PMU 1
 TRIGGERING
See page 5-129.
MESSAGE
 PMU 1
 RECORDING
See page 5-137.