EasyManua.ls Logo

GE D60 - Page 384

GE D60
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-250 D60 Line Distance Protection System GE Multilin
5.6 GROUPED ELEMENTS 5 SETTINGS
5
Figure 5–127: PHASOR DIAGRAM
The function approximates the voltage rise at the far end of the transmission line according to the following relationship:
(EQ 5.23)
In the above equation:
V_1 is the positive-sequence voltage (phasor quantity) in secondary volts measured at the local terminal.
I_1 is the positive-sequence current (phasor quantity) in secondary amps measured at the local terminal.
V
nominal
is the phase VT secondary setting in the case of wye VTs and the phase VT secondary setting dividec by 3 in
the case of delta VTs.
Z
C_mag
and Z
C_ang
represent an impedance between the local and remote terminals.
V_1
C
is the calculated positive-sequence voltage magnitude at the remote terminal.
If the magnitude of Z
C
is set to one-half the series impedance of the line (R + jX
L
), the compensated voltage will be approx-
imately equal to the positive-sequence voltage at the remote end of the line. A more accurate setting of Z
C
may be made if
the positive-sequence charging current and the voltages at the local and remote line ends resulting from an open breaker
are known. In this case, the desired reach setting would be:
(EQ 5.24)
The following settings are available.
COMPENSATED OV Zc MAG: This setting specifies the magnitude of the impedance Z
C
in secondary ohms. This
should be set to half the positive-sequence series impedance of the line. Alternately, if the positive-sequence charging
currents and local and remote voltages are known, then this value can be calculated from equation above.
COMPENSATED OV Zc ANG: This setting specifies the angle of the impedance Z
C
in degrees.
COMPENSATED OV I_1max: This setting specifies the maximum expected positive-sequence line current for which a
remote overvoltage is anticipated.
COMPENSATED OV STG1 PKP, COMPENSATED OV STG2 PKP, COMPENSATED OV STG3 PKP: These settings
specify the pickup level for each of the three stages. If any stage is set with no intentional time delay, then the pickup
setting should be set 15% above the anticipated steady state overvoltage to prevent an operation during line energiza-
tion. A stage that is not used may be set to its maximum setting value (3.000 pu) to effectively disable it.
COMPENSATED OV STG1 DELAY, COMPENSATED OV STG2 DELAY, COMPENSATED OV STG3 DELAY: These
settings specify the time delay for each of the three stages in seconds.
The compensated overvoltage scheme logic is shown below.
843811A1.CDR
V_1
V_1
c
I_1
I_1 × Z
c
V_1
C
pu
V_1 I_1 Z
C_mag
e
jZ
C_ang

V
nominal
-------------------------------------------------------------------------------
=
Z
C
V
local
V
remote
I
ch earg
----------------------------------------
=

Table of Contents

Related product manuals