GE Multilin D60 Line Distance Protection System 5-253
5 SETTINGS 5.6 GROUPED ELEMENTS
5
Figure 5–129: DIRECTIONAL POWER CHARACTERISTIC
By making the characteristic angle adjustable and providing for both negative and positive values of the minimum operating
power a variety of operating characteristics can be achieved as presented in the figure below. For example, section (a) in
the figure below shows settings for reverse power, while section (b) shows settings for low forward power applications.
Figure 5–130: DIRECTIONAL POWER ELEMENT SAMPLE APPLICATIONS
RESTRAIN
SMIN
RCA+
CALIBRATION
+
-
OPERATE
Direction
Q
P
842702A1.CDR
P
Q
OPERATE
RESTRAIN
RCA = 0
o
SMIN > 0
(d)
P
Q
OPERATE RESTRAIN
RCA = 180
o
SMIN > 0
(a)
P
Q
OPERATE
RESTRAIN
RCA = 0
o
SMIN < 0
(c)
P
Q
OPERATE
RESTRAIN
RCA = 180
o
SMIN < 0
(b)
P
Q
OPERATE
RESTRAIN
RCA = 90
o
SMIN > 0
(e)
P
Q
OPERATE
RESTRAIN
RCA = 270
o
SMIN < 0
(f)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D60 and is the answer not in the manual?

GE D60 Specifications

General IconGeneral
Frequency50/60 Hz
ManufacturerGeneral Electric (GE)
Communication ProtocolsDNP3
MountingPanel mount
Operating Temperature-20°C to +60°C

Related product manuals