5-322 D60 Line Distance Protection System GE Multilin
5.7 CONTROL ELEMENTS 5 SETTINGS
5
In single-bit applications, DUTT RX1 must be used. In two-bit applications, DUTT RX1 and DUTT RX2 must be used. In
four-bit applications, DUTT RX1, DUTT RX2, DUTT RX3, and DUTT RX4 must be used. In multi-terminal applications, the RX
signals from two or more remote terminals should be connected through OR gates in the FlexLogic and the resulting
signals should be configured as the
DUTT RX inputs.
Figure 5–165: DUTT SCHEME LOGIC
SETTING
SETTINGS
SETTINGS
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
DUTT SCHEME
FUNCTION:
DUTTNOOFCOMM
BITS:
DUTTNOOFCOMM
BITS:
DUTTNOOFCOMM
BITS:
Enabled = 1
Off=0
Off=0
Off=0
Off=0
PH DIST Z1 PKP
DUTT RX1:
DUTT RX2:
DUTT RX3:
DUTT RX4:
DUTT TX1
DUTT TRIP A
DUTT TRIP B
DUTT TRIP C
DUTT TRIP 3P
DUTT TX2
DUTT TX3
DUTT TX4
DUTT OP
DUTT SEAL-IN
DELAY:
TRANSMIT TABLE
TRIP TABLE
Phase
Selector
Phase
Selector
RX
RUN
RUN
Disabled = 0
837012AD.CDR
GND DIST Z1 PKP
OR
OR
AND
AND
t
R
S
T
0
SETTING
DUTT SCHEME BLOCK:
OFF = 0
AND
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP
FLEXLOGIC OPERANDS
AR FORCE 3P TRIP
OPEN POLE OP