GE Multilin D60 Line Distance Protection System 5-329
5 SETTINGS 5.7 CONTROL ELEMENTS
5
e) PERMISSIVE OVER-REACHING TRANSFER TRIP (POTT1)
PATH: SETTINGS CONTROL ELEMENTS PILOT SCHEMES POTT1 SCHEME
POTT1 SCHEME
POTT1 SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POTT1 SCHEME BLOCK:
Off
Range: FlexLogic operand
MESSAGE
POTT1 PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled, Custom
MESSAGE
POTT1 ECHO COND:
Off
Range: FlexLogic operand
MESSAGE
POTT1 RX PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO DURATION:
0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO LOCKOUT:
0.250 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE END OPEN PICKUP
DELAY: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
POTT1 SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DIR FWD1:
Off
Range: FlexLogic operand
MESSAGE
DIR FWD2:
Off
Range: FlexLogic operand
MESSAGE
DIR FWD3:
Off
Range: FlexLogic operand
MESSAGE
POTT1 NO OF COMM
BITS: 1
Range: 1, 2, or 4
MESSAGE
POTT1 RX1:
Off
Range: FlexLogic operand
MESSAGE
POTT1 RX2:
Off
Range: FlexLogic operand
MESSAGE
POTT1 RX3:
Off
Range: FlexLogic operand
MESSAGE
POTT1 RX4:
Off
Range: FlexLogic operand
MESSAGE
POTT1 SCHEME TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
POTT1 SCHEME EVENTS:
Disabled
Range: Disabled, Enabled