EasyManua.ls Logo

GE D60 - Page 637

GE D60
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin D60 Line Distance Protection System B-15
APPENDIX B B.4 MEMORY MAPPING
B
15CA Direct Inputs/Outputs Unreturned Message Count - Ch. 1 0 to 65535 --- 1 F001 0
15CB Direct Inputs/Outputs Unreturned Message Count - Ch. 2 0 to 65535 --- 1 F001 0
15D0 Direct Device States 0 to 65535 --- 1 F500 0
15D1 Reserved 0 to 65535 --- 1 F001 0
15D2 Direct Inputs/Outputs CRC Fail Count 1 0 to 65535 --- 1 F001 0
15D3 Direct Inputs/Outputs CRC Fail Count 2 0 to 65535 --- 1 F001 0
Field Unit Input/Output States (Read Only)
15E0 Field Unit Contact Input States (3 items) 0 to 65535 --- 1 F500 0
15E3 Field Unit Contact Input Output Operand States (8 items) 0 to 65535 --- 1 F500 0
15EB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
15F3 Field Contact Output Current States (8 items) 0 to 65535 --- 1 F500 0
15FB Field Contact Output Physical States (8 items) 0 to 65535 --- 1 F500 0
1603 Field Shared Input States 0 to 65535 --- 1 F500 0
1604 Field Shared Input Channel States 0 to 65535 --- 1 F500 0
1605 Field Shared Input Test States 0 to 65535 --- 1 F500 0
1606 Field Shared Output Operand States 0 to 65535 --- 1 F500 0
1607 Field Latching Output Open Operand States 0 to 65535 --- 1 F500 0
1608 Field Latching Output Close Operand States 0 to 65535 --- 1 F500 0
1609 Field Latching Output Open Driver States 0 to 65535 --- 1 F500 0
160A Field Latching Output Close Driver States 0 to 65535 --- 1 F500 0
160B Field Latching Output Physical States 0 to 65535 --- 1 F500 0
160C Field Unit Online/Offline States 0 to 65535 --- 1 F500 0
160D Field RTD Input Trouble States 0 to 65535 --- 1 F500 0
160E Field Transducer Input Trouble States 0 to 65535 --- 1 F500 0
Ethernet Fibre Channel Status (Read/Write)
1610 Ethernet Primary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet Secondary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1612 Ethernet Tertiary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data Logger Channel Count 0 to 16 channel 1 F001 0
1619 Time of Oldest Available Samples 0 to 4294967295 seconds 1 F050 0
161B Time of Newest Available Samples 0 to 4294967295 seconds 1 F050 0
161D Data Logger Duration 0 to 999.9 days 0.1 F001 0
Sensitive Directional Power Actuals (Read Only) (2 Modules)
1680 Sensitive Directional Power 1 Power
-2147483647 to 2147483647
W1F060 0
1682 Sensitive Directional Power 2 Power
-2147483647 to 2147483647
W1F060 0
Field Unit RTD Actuals (Read Only) (8 Modules)
16C0 Field RTD x Value -32768 to 32767 °C 1 F002 0
16C1 ...Repeated for module number 2
16C2 ...Repeated for module number 3
16C3 ...Repeated for module number 4
16C4 ...Repeated for module number 5
16C5 ...Repeated for module number 6
16C6 ...Repeated for module number 7
16C7 ...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 Modules)
16C8 Field Transducer x Value -32.768 to 32.767 --- 0.001 F004 0
16CA ...Repeated for module number 2
16CC ...Repeated for module number 3
16CE ...Repeated for module number 4
16D0 ...Repeated for module number 5
16D2 ...Repeated for module number 6
16D4 ...Repeated for module number 7
16D6 ...Repeated for module number 8
Table B–10: MODBUS MEMORY MAP (Sheet 7 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents

Related product manuals