B-26 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
Field Unit Process Card Ports (Read/Write Setting)
3878 Field Unit 1 Process Card Port 0 to 7 --- 1 F244 6 (H1a)
3879 Field Unit 2 Process Card Port 0 to 7 --- 1 F244 4 (H2a)
387A Field Unit3 Process Card Port 0 to 7 --- 1 F244 2 (H3a)
387B Field Unit 4 Process Card Port 0 to 7 --- 1 F244 0 (H4a)
387C Field Unit 5 Process Card Port 0 to 7 --- 1 F244 7 (H1b)
387D Field Unit 6 Process Card Port 0 to 7 --- 1 F244 5 (H2b)
387E Field Unit 7 Process Card Port 0 to 7 --- 1 F244 3 (H3b)
387F Field Unit 8 Process Card Port 0 to 7 --- 1 F244 1 (H4b)
Field Unit CT VT Settings (Read/Write Setting) (6 Modules)
3890 Remote Phase CT x Origin 1 0 to 16 --- 1 F247 0 (none)
3891 Remote Phase CT x Origin 2 0 to 16 --- 1 F247 0 (none)
3892 Remote Ground CT x Origin 1 0 to 16 --- 1 F248 0 (none))
3893 Remote Ground CT x Origin 2 0 to 16 --- 1 F248 0 (none)
3894 AC Bank Redundancy Type 0 to 2 --- 1 F261 1 (Dependability
Biased)
3895 Remote Phase CT 1 Primary 1 to 65000 --- 1 F001 1
3896 Remote Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
3897 Remote Ground CT 1 Primary 1 to 65000 --- 1 F001 1
3898 Remote Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
3899 Remote Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
389A Remote Phase VT 1 Secondary 25 to 240 --- 0.1 F001 664
389B Remote Phase VT 1 Ratio 1 to 24000 --- 1 F060 1
389D Remote Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
389E Remote Auxiliary VT 1 Secondary 25 to 240 --- 0.1 F001 664
389F Remote Auxiliary VT 1 Ratio 1 to 24000 --- 1 F060 1
38A1 ...Repeated for module number 2
38B2 ...Repeated for module number 3
38C3 ...Repeated for module number 4
38D4 ...Repeated for module number 5
38E5 ...Repeated for module number 6
Field Unit Contact Inputs (Read/Write Setting) (40 Modules)
3900 Field Contact Input 1 ID --- --- --- F205 "FCI 1"
3906 Field Contact Input 1 Origin 0 to 8 --- 1 F256 0 (none)
3907 Field Contact Input 1 Input 1 to 18 --- 1 F001 1
3908 Field Contact Input 1 Failsafe Value 0 to 1 --- 1 F108 0 (Off)
3909 Field Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20
390A Field Contact Input 1 Events 0 to 1 --- 1 F102 1 (Enabled)
390B ...Repeated for Field Contact Input 2
3916 ...Repeated for Field Contact Input 3
3921 ...Repeated for Field Contact Input 4
392C ...Repeated for Field Contact Input 5
3937 ...Repeated for Field Contact Input 6
3942 ...Repeated for Field Contact Input 7
394D ...Repeated for Field Contact Input 8
3958 ...Repeated for Field Contact Input9
3963 ...Repeated for Field Contact Input 10
396E ...Repeated for Field Contact Input 11
3979 ...Repeated for Field Contact Input 12
3984 ...Repeated for Field Contact Input 13
398F ...Repeated for Field Contact Input 14
399A ...Repeated for Field Contact Input 15
39A5 ...Repeated for Field Contact Input 16
39B0 ...Repeated for Field Contact Input 17
Table B–10: MODBUS MEMORY MAP (Sheet 18 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT