GE Multilin D60 Line Distance Protection System B-35
APPENDIX B B.4 MEMORY MAPPING
B
47DF Breaker 1 External Alarm 0 to 4294967295 --- 1 F300 0
47E1 Breaker 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
47E3 Breaker 1 Pushbutton Control 0 to 1 --- 1 F102 0 (Disabled)
47E4 Breaker 1 Manual Close Recall Time 0 to 4294967295 s 0.001 F003 0
47E6 Breaker 1 Out of Service 0 to 4294967295 --- 1 F300 0
47E8 Breaker 1 Block Open 0 to 4294967295 --- 1 F300 0
47EA Breaker 1 Block Close 0 to 4294967295 --- 1 F300 0
47EC Breaker 1 Phase A / Three-pole Opened 0 to 4294967295 --- 1 F300 0
47EE Breaker 1 Phase B Opened 0 to 4294967295 --- 1 F300 0
47F0 Breaker 1 Phase C Opened 0 to 4294967295 --- 1 F300 0
47F2 Breaker 1 Operate Time 0 to 65.535 s 0.001 F001 70
47F3 Breaker 1 Events 0 to 1 --- 1 F102 0 (Disabled)
47F4 Reserved 0 to 65535 s 1 F001 0
47F5 ...Repeated for breaker 2
481A ...Repeated for breaker 3
483F ...Repeated for breaker 4
Compensated Overvoltage (Read/Write Grouped Setting)
48F0 Compensated OV Function 0 to 1 --- 1 F102 0 (Disabled)
48F1 Compensated OV Sourced 0 to 5 --- 1 F167 0 (SRC 1)
48F2 Compensated OV Zc Mag 0 to 500 ohm 0.01 F001 200
48F3 Compensated OV Zc Ang 30 to 90 degree 1 F001 90
48F4 Compensated OV I_1max 0.01 to 1 pu 0.01 F001 20
48F5 Compensated OV STG1 PKP 0.25 to 3 pu 0.001 F001 1300
48F6 Compensated OV STG1 Delay 0 to 600 sec 0.01 F001 100
48F7 Compensated OV STG2 PKP 0.25 to 3 pu 0.001 F001 1300
48F8 Compensated OV STG2 Delay 0 to 600 sec 0.01 F001 100
48F9 Compensated OV SGT3 PKP 0.25 to 3 pu 0.001 F001 1300
48FA Compensated OV STG3 Delay 0 to 600 sec 0.01 F001 100
48FB Compensated OV Block 0 to 4294967295 --- 1 F300 0
48FD Compensated OV Target 0 to 2 --- 1 F109 0 (Self-reset)
48FE Compensated OV Events 0 to 1 --- 1 F102 0 (Disabled)
FlexCurve A (Read/Write Setting)
4910 FlexCurve A (120 items) 0 to 655535 ms 1 F011 0
FlexCurve B (Read/Write Setting)
4988 FlexCurve B (120 items) 0 to 655535 ms 1 F011 0
Modbus User Map (Read/Write Setting)
4A00 Modbus Address Settings for User Map (256 items) 0 to 65535 --- 1 F001 0
User Displays Settings (Read/Write Setting) (16 Modules)
4C00 User-Definable Display 1 Top Line Text --- --- --- F202
4C0A User-Definable Display 1 Bottom Line Text --- --- --- F202 ““
4C14 Modbus Addresses of Display 1 Items (5 items) 0 to 65535 --- 1 F001 0
4C19 Reserved (7 items) --- --- --- F001 0
4C20 ...Repeated for User-Definable Display 2
4C40 ...Repeated for User-Definable Display 3
4C60 ...Repeated for User-Definable Display 4
4C80 ...Repeated for User-Definable Display 5
4CA0 ...Repeated for User-Definable Display 6
4CC0 ...Repeated for User-Definable Display 7
4CE0 ...Repeated for User-Definable Display 8
4D00 ...Repeated for User-Definable Display 9
4D20 ...Repeated for User-Definable Display 10
4D40 ...Repeated for User-Definable Display 11
4D60 ...Repeated for User-Definable Display 12
4D80 ...Repeated for User-Definable Display 13
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT