B-54 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
81C2 Reserved Register T3 -2147483647 to
2147483647
--- 1 F004 0
81C4 Reserved Register T4 0 to 4294967295 --- 1 F003 0
81C6 Reserved Register T5 0 to 4294967295 --- 1 F003 0
81C8 Reserved Register T6 0 to 4294967295 --- 1 F003 0
81CA Reserved Register T7 0 to 4294967295 --- 1 F003 0
81CC Reserved Register T8 0 to 4294967295 --- 1 F003 0
Breaker Failure (Read/Write Grouped Setting) (6 Modules)
8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)
8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)
8605 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 --- 1 F300 0
8607 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 0
8609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860A Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860B Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)
860C Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0
860D Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)
860E Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0
860F Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)
8610 Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 0
8611 Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 4294967295 --- 1 F300 0
8613 Breaker Failure 1 Breaker Status 2 Phase A/3P 0 to 4294967295 --- 1 F300 0
8615 Breaker Failure 1 Breaker Test On 0 to 4294967295 --- 1 F300 0
8617 Breaker Failure 1 Phase Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 1050
8618 Breaker Failure 1 Neutral Amp Hiset Pickup 0.001 to 30 pu 0.001 F001 1050
8619 Breaker Failure 1 Phase Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050
861A Breaker Failure 1 Neutral Amp Loset Pickup 0.001 to 30 pu 0.001 F001 1050
861B Breaker Failure 1 Loset Time 0 to 65.535 s 0.001 F001 0
861C Breaker Failure 1 Trip Dropout Delay 0 to 65.535 s 0.001 F001 0
861D Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
861E Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)
861F Breaker Failure 1 Phase A Initiate 0 to 4294967295 --- 1 F300 0
8621 Breaker Failure 1 Phase B Initiate 0 to 4294967295 --- 1 F300 0
8623 Breaker Failure 1 Phase C Initiate 0 to 4294967295 --- 1 F300 0
8625 Breaker Failure 1 Breaker Status 1 Phase B 0 to 4294967295 --- 1 F300 0
8627 Breaker Failure 1 Breaker Status 1 Phase C 0 to 4294967295 --- 1 F300 0
8629 Breaker Failure 1 Breaker Status 2 Phase B 0 to 4294967295 --- 1 F300 0
862B Breaker Failure 1 Breaker Status 2 Phase C 0 to 4294967295 --- 1 F300 0
862D ...Repeated for Breaker Failure 2
865A ...Repeated for Breaker Failure 3
8687 ...Repeated for Breaker Failure 4
86B4 ...Repeated for Breaker Failure 5
86E1 ...Repeated for Breaker Failure 6
FlexState Settings (Read/Write Setting)
8800 FlexState Parameters (256 items) 0 to 4294967295 --- --- F300 0
Digital Elements (Read/Write Setting) (48 Modules)
8A00 Digital Element 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8A01 Digital Element 1 Name --- --- --- F203 “Dig Element 1“
8A09 Digital Element 1 Input 0 to 4294967295 --- 1 F300 0
8A0B Digital Element 1 Pickup Delay 0 to 999999.999 s 0.001 F003 0
8A0D Digital Element 1 Reset Delay 0 to 999999.999 s 0.001 F003 0
Table B–10: MODBUS MEMORY MAP (Sheet 46 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT