B-66 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
B228 ...Repeated for Received Analog 13
B22A ...Repeated for Received Analog 14
B22C ...Repeated for Received Analog 15
B22E ...Repeated for Received Analog 16
B230 ...Repeated for Received Analog 17
B232 ...Repeated for Received Analog 18
B234 ...Repeated for Received Analog 19
B236 ...Repeated for Received Analog 20
B238 ...Repeated for Received Analog 21
B23A ...Repeated for Received Analog 22
B23C ...Repeated for Received Analog 23
B23E ...Repeated for Received Analog 24
B240 ...Repeated for Received Analog 25
B242 ...Repeated for Received Analog 26
B244 ...Repeated for Received Analog 27
B246 ...Repeated for Received Analog 28
B248 ...Repeated for Received Analog 29
B24A ...Repeated for Received Analog 30
B24C ...Repeated for Received Analog 31
B24E ...Repeated for Received Analog 32
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290 IEC 61850 configurable reports dataset items (64 items) 0 to 848 --- 1 F615 0 (None)
Wattmetric Ground Fault Settings (read/write grouped, 5 Modules)
B300 Wattmetric ground fault 1 function 0 to 1 --- 1 F102 0 (Disabled)
B301 Wattmetric ground fault 1 source 0 to 5 --- 1 F167 0 (SRC 1)
B302 Wattmetric ground fault 1 voltage 0 to 1 --- 1 F234 0 (Calculated VN)
B303 Wattmetric ground fault 1 overvoltage pickup 0.02 to 3.00 pu 0.01 F001 20
B304 Wattmetric ground fault 1 current 0 to 1 --- 1 F235 0 (Calculated IN)
B305 Wattmetric ground fault 1 overcurrent pickup 0.002 to 30.000 pu 0.001 F001 60
B306 Wattmetric ground fault 1 overcurrent pickup delay 0 to 600 s 0.01 F001 20
B307 Wattmetric ground fault 1 power pickup 0.001 to 1.2 pu 0.001 F001 100
B308 Wattmetric ground fault 1 ECA 0 to 360 ° Lag 1 F001 0
B309 Wattmetric ground fault 1 power pickup delay 0 to 600 s 0.01 F001 20
B30A Wattmetric ground fault 1 curve 0 to 5 --- 1 F236 0 (Definite Time)
B30B Wattmetric ground fault 1 multiplier 0.01 to 2 s 0.01 F001 100
B30C Wattmetric ground fault 1 block 0 to 65535 --- 1 F300 0
B30E Wattmetric ground fault 1 target 0 to 2 --- 1 F109 0 (Self-reset)
B30F Wattmetric ground fault 1 events 0 to 1 --- 1 F102 0 (Disabled)
B310 Wattmetric ground fault 1 reference power 0.001 to 1.2 pu 0.001 F001 500
B311 Wattmetric ground fault x Reserved 0 to 1 --- 1 F001 0
B312 ...Repeated for wattmetric ground fault 2
B324 ...Repeated for wattmetric ground fault 3
B336 ...Repeated for wattmetric ground fault 4
B348 ...Repeated for wattmetric ground fault 5
Wattmetric Ground Fault Actual Values (Read Only) (5 Modules)
B360 Wattmetric ground fault 1 operating power 0 to 999999.999 W 0.001 F060 0
B362 ...Repeated for wattmetric ground fault 2
B364 ...Repeated for wattmetric ground fault 3
B366 ...Repeated for wattmetric ground fault 4
B368 ...Repeated for wattmetric ground fault 5
IEC 61850 XSWI Configuration (Read/Write Setting) (24 Modules)
B370 Flexlogic Operand for IEC 61850 XSWI.ST.Loc Status 0 to 4294967295 --- 1 F300 0
IEC 61850 XSWI Configuration (Read/Write Command) (24 Modules)
B372 Command to Clear XSWI OpCnt (Operation Counter) 0 to 1 --- 1 F126 0 (No)
Table B–10: MODBUS MEMORY MAP (Sheet 58 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT