EasyManua.ls Logo

GE D60 - Page 722

GE D60
826 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B-100 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
F253
ENUMERATION: BRICK TRANSDUCER ORIGIN
F256
ENUMERATION: BRICK ORIGIN/DESTINATION
F259
ENUMERATION: BRICK RTD TYPE
0 = 100 Ohm Nickel, 1 = 120 Ohm Nickel, 2 = 100 Ohm Platinum
F260
ENUMERATION: DATA LOGGER MODE
0 = Continuous, 1 = Trigger
F261
ENUMERATION: BANK REDUNDANCY TYPE
0 = None, 1 = Dependability Biased, 2 = Security Biased
F262
ENUMERATION: BRICK STATUS
0 = Disabled, 1 = OK, 2 = Communications Trouble, 3 = Equip-
ment Mismatch, 4 = Brick Trouble
F270
ENUMERATION: FAULT REPORT VT SUBSTITUTION
F300
UR_UINT32: FLEXLOGIC BASE TYPE (15-bit type)
The FlexLogic BASE type is 7 bits and is combined with an 8-bit
descriptor and 1 bit for protection element to form a 16-bit value.
The combined bits are of the form: PTTTTTTTDDDDDDDD,
where P bit if set, indicates that the FlexLogic type is associated
with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor.
The values in square brackets indicate the base type with P prefix
[PTTTTTTT] and the values in round brackets indicate the descrip-
tor range. The right most T bit indicates whether the type is an ON
or OFF type. There can be a total of 64 types (plus protection ele-
ments). There can be a total of 256 descriptors of each type.
[0] Off (0) – this is boolean FALSE value
[1] On (1) – this is boolean TRUE value
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 32)
[6] VIRTUAL OUTPUTS (1 to 64
[8] CONTACT OUTPUTS
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64)
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[16] DIRECT INPUTS (1 to 96)
[18] REMOTE OUTPUT DNA BIT PAIRS (1 to 32)
[20] REMOTE OUTPUT UserSt BIT PAIRS (1 to 32)
[22] REMOTE DEVICE ONLINE (1 to 16)
[24] MISCELLANEOUS EQUATION
[26] TELEPROTECTION INPUTS
[28] INSERT (via keypad only)
[30] DELETE (via keypad only)
[32] END
[34] NOT (1 INPUT)
[36] 2 INPUT XOR (0)
[38] LATCH SET/RESET (2 inputs)
[40] OR (2 to 16 inputs)
[42] AND (2 to 16 inputs)
[44] NOR (2 to 16 inputs)
[46] NAND (2 to 16 inputs)
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 64)
[52] ONE SHOT
[54] SELF-TEST ERROR (see F141 for range)
[56] PLATFORM DIRECT INPUT (1 to 96)
4U2/AC8
5U3/AC4
6U3/AC8
7U4/AC4
8U4/AC8
9U5/AC4
10 U5/AC8
11 U6/AC4
12 U6/AC8
13 U7/AC5
14 U7/AC8
15 U8/AC5
16 U8/AC8
Value Description
0None
1 U1/DC1
2 U1/DC2
3 U1/DC3
4 U2/DC1
... ...
24 U8/DC3
Value Description
0None
1U1
2U2
3U3
4U4
5U5
6U6
7U7
8U8
Value Description
Value Description
0None
1I_0
2V_0

Table of Contents