GE Multilin D60 Line Distance Protection System B-103
APPENDIX B B.4 MEMORY MAPPING
B
F551
ENUMERATION: RTD TRIP VOTING
F552
ENUMERATION: RTD INPUT OPEN
F563
ENUMERATION: DSCP TYPE
F600
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value used when this
parameter is selected. Only certain values may be used as Flex-
Analogs (basically all metering quantities used in protection).
F601
ENUMERATION: COM2 PORT USAGE
F605
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
F606
ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
F607
ENUMERATION: OPEN POLE DETECTOR MODE
F608
ENUMERATION: OPEN POLE DETECTION FUNCTION
F609
ENUMERATION: TRIP OUTPUT TRIP RESET FUNCTION
F610
ENUMERATION: SINGLE-POLE AUTORECLOSE INITIATION
MODE
Enumeration RTD trip voting
0None
1Group
2 RTD Input 1
3 RTD Input 2
4 RTD Input 3
5 RTD Input 4
6 RTD Input 5
7 RTD Input 6
8 RTD Input 7
9 RTD Input 8
10 RTD Input 9
11 RTD Input 10
12 RTD Input 11
13 RTD Input 12
Enumeration RTD open
0None
1Alarm
2Block
Enumeration DSCP type
0None
1 Expedited Forwarding
Enumeration COM2 port usage
0 RS485
1RRTD
2 GPM-F
3 RRTD and GPM-F
Enumeration Remote DPS input status
0 Intermediate
1Off
2On
3Bad
Enumeration Remote double-point status input
0None
1 Remote input 1
2 Remote input 2
3 Remote input 3

64 Remote input 64
Enumeration Open Pole Mode
0 Accelerated
1 Traditional
Enumeration Open Pole Detection
0 I AND V AND CBaux
1 I AND V only
Enumeration Trip Reset
0 Pole Curr OR Custom
1 CBaux OR Custom
2Custom
Enumeration Initiation Mode
0 Protection AND CB
1 Protection Only