EasyManua.ls Logo

GE Digital Energy LP 33 - RPA System - Control Bus Connection

GE Digital Energy LP 33
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
g
G
E
OPM_LPS_33E_10K_30K_4CN_V010.doc 33/82 Operating Manual LP 33 / 10-20-30 kVA
4.8.4 RPA system - Control bus connection
WARNING !
This operation must be performed by trained personnel before the initial start-
up (ensure that the UPS installation is completely powered down).
Access to the RPA board
1 - Open the front door A of the cabinet.
2 - Remove the protection covers B, C, D
fixed with screws F.
3 - Remove the front panel protection cover C
by pulling it off.
SGT4000_010-020_RPA connection_01
F
A
E
D
B
F
C
F
Fig. 4.8.4-1 Access to the RPA board
NOTE !
When fixing again the protection
covers, make sure that the
screws “F” are as tight as
possible since they serve also as
earth connection.
SGT4000_010-020_RPA connection_02GB
UPS 2
P16
J3
J4
UPS 3
P16
J3
J4
P16
UPS 4
J4
J3
P2 P2 P2 P2
P15 P15 P15 P15
P16
J4
J3
UPS 1
Fig. 4.8.4-2 Bus connection RPA parallel system
Bus connection RPA parallel system
Connect the control bus cable between the parallel units as indicated in the diagram Fig. 4.8.4-2.
Provide that the connectors J3 and J4 are properly fixed with the included screws.
The jumper JP1 - JP2 - JP3 must be
removed only on the intermediate units,
where the connectors J3 and J4 are both
inserted.
Do not insert or remove J3 and J4 from
the board “P16 - Connector adapter RPA”
when the parallel system is operating.
SGT4000_010-020_RPA connection_03
JP2JP1
JP3
P16
J3
J4
Fig. 4.8.4-3 Connection to Board P16

Table of Contents

Related product manuals