OPM_LPS_33E_10K_30K_4CN_V010.doc 40/82 Operating Manual LP 33 / 10-20-30 kVA
7 LCD SCREEN
Shows the UPS system data, events messages and UPS setting.
The data is displayed on 2 rows, 20 characters each, allowing the operator to select between 2
languages: English and Chinese.
If there is no keypad activity during 1 minute the LCD screen will return to default screen.
7.1 METERING SCREENS (Metering)
This menu allows, when the keypad Metering is pressed, to show on the LCD panel a series of
screens containing metering information about AC and DC parameters.
LP 33 20kVA P1
APPLICATION ON UPS
1. UPS family, nominal rating and for RPA: P + No. UPS.
2. Load status: application on UPS, on utility, supply off,
manual bypass (appl. on manual dev.) and IEM mode.
Load = 70%
Autonomy = 7min
1. The load amount as a percentage of the nominal load
(referred to the most loaded phase).
2. Estimated battery backup time with actual load.
Udc Voltage
Udcp=400V Udcn=400V
1. Booster DC voltage information screen.
2. Booster DC voltage + pole (Udcp) and – pole (Udcn).
Battery Voltage
Ubp=273V Ubn=273V O
1. Battery DC voltage information screen.
2. Battery DC voltage + pole (Ubp), – pole (Ubn) and the
status SBM (Superior Battery Management).
The functionality of SBM can help to reduce the Battery recharging time, and improve the
lifetime of the Battery.Beside the indication of the Battery voltage on the display, a letter
shows, according to the table below, the operational status of SBM:
Sigle Status of charger Charter voltage Description
O
OFF 0 VDC
T
ON Boost (294 VDC) Boost charge with new Battery
F
ON Floating (273 VDC) Battery charged
L
ON Floating (273 VDC) Normal charge
B
ON Boost (294 VDC) Boost charge
E
ON Boost (294 VDC) Battery equalization
Access to the Parameters for setting the SBM mode is password protected.
Please call your Service Centre.
Charge Level = 100%
Autonomy = 7min
1. Battery charge level.
2. Estimated battery backup time with actual load.
Mains U1=228V
U2=230V U3=229V
1. Mains input voltage information screen and mains input line
voltage L1 phase.
2. MAINS INPUT LINE VOLTAGE L2 AND L3 PHASES.
Mains frequency
f=50.0Hz
1. Mains input frequency information screen.
2. MAINS INPUT FREQUENCY.