OPM_LPS_33E_10K_30K_4CN_V010.doc 53/82 Operating Manual LP 33 / 10-20-30 kVA
7. Modem alarm enable / disable
Modem Alarm Enabled
NO
1. Modem alarm enable/disable.
2. YES/NO controls the automatic events signalling through
modem.
If this parameter is set to YES the UPS itself will call the
remote location when a new event occurs.
8. Modem alarm delay
Modem Alarm Delay
30
1. Modem alarm delay.
2. This parameter controls the delay between the occurrence
of a new event and the modem dialling.
It is useful because since the events typically do not occur
isolated but in certain sequences, you can eliminate the
need for multiple dial-outs for such a sequence of events.
9. Telephone number 1
Telephone Number 1
000
1. Telephone number 1.
2. This parameter specifies a first tel. number to be used for
modem dial-out.
The telephone number has a maximum of 39 characters
and cannot contain intermediate blank.
If the desired number is shorter than 39 characters, finish
the string with blanks.
10. Telephone number 1 enable / disable
Tel. Number 1 Enable
NO
1. Telephone number 1 enable/disable.
2. This parameter YES/NO specifies if the first telephone
number will be used for dial-out.
11/13/15. Telephone number 2/3/4
Telephone Number 2/3/4
000
1. Telephone number 2/3/4.
2. It records the second/third/fourth dial-out number.
12/14/16. Telephone number 2/3/4 enable / disable
Tel. Number 2/3/4 Enable
NO
1. Telephone number 2/3/4 enable/disable.
2. This parameter YES/NO specifies if the second/third/fourth
telephone number will be used for dial-out.
17. Operation mode selection (On-line or IEM)
IEM Enable
YES
The IEM (Intelligent Energy Management) mode
can only be activated on single units.
1. IEM mode This parameter (values YES/NO) enables or disables the operation in IEM mode.
If the value is YES and the current time is in the interval for the current day, the IEM mode is active.
The activation / disactivation of IEM mode is indicated each time in the event list.
In order to check the inverter function, at least 1 minute of On-line mode must be programmed
during the week (the YES/NO parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in On-line mode is not respected, the IEM mode will be disabled.
If the value is NO, the UPS is normally operating in On-line/double conversion mode at all times.