EntelliGuard®TU Trip Unit
09/25/08 Appendix 1 Communications Parameters
© 2008 General Electric All Rights Reserved 27
Register Variable Value Read/Write
2–GF&ST
3–ST
6–ST and Inst
7–GF, ST and Inst
208 PT Primary Voltage 120–600 Read/Write
209 PT Connection 0–Ph-N, 1–Ph-Ph Read/Write
210 Password Protection 0 to 20, 16Lock, 19–Unlock Read/Write
211 Modbus Slave Address 8 bit value Read/Write
212 Profibus Slave Address 8 bit value Read/Write
213 Communication Setting 0–300-8N1
1–600-8N1
2–1200-8N1
3–400-8N1
4–4800-8N1
5–9600-8N1
6–19200-8N1
7–300-8O1
8–600-8O1
9–1200-8O1
10–2400-8O1
11–4800-8O1
12–9600-8O1
13–19200-8O1
14–300-8E1
15–600-8E1
16–1200-8E1
17–2400-8E1
18–4800-8E1
19–9600-8E1
Read/Write
215 Long Time Trip Pickup 1–0.5
2–0.55
10–9.5
11–1.0
Read/Write
216 Long Time Trip Delay 0–Off
1–C Min
24–F 2
44–F Max
Read/Write
217 Long Time Cooling Constant 0–No Cooling, 1–12 Minute Cooling Read/Write
219 Protective Relay Trip Enable 0–Disable, 1–Enable Read/Write
220 Frequency 0–50 Hz, 1–60 Hz, 1–400 Hz Read/Write
222 Short Time Trip Pickup 1–1.5
2–2.0
Read/Write
223 Short Time Trip Delay 0–Off
1–Band1
2–Band2
16–Band 16
17–Band 17
Read/Write
224 Short Time Slope 0–No Slope
1
2
3
Read/Write
225 Instantaneous Trip Pickup 0–Off (For switchable Inst Only)
2–2
43–29
44–30
Read/Write
226 Reduced Instantaneous Trip Pickup 1–1.5
2–2
27–14.5
28–15
Read/Write
227 GF CT Trip Pickup 11–0.2
2–0.11
Read/Write