RX3i Ethernet Interface Module IC695ETM001-HV IPI 3
February 2016 GFK-2332W
Indicator Light Emitting Diodes (LEDs)
LED
State Indicates
ETHERNET OK
LAN OK
LOG EMPTY
Fast Blink
Off
Off
Performing Diagnostics
ETHERNET OK
LAN OK
LOG EMPTY
Slow Blink
Off
Off
Waiting for Ethernet configuration
from CPU
ETHERNET OK
LAN OK
LOG EMPTY
Slow Blink
†
On/Traffic/Off
Slow Blink
†
(† EOK and STAT
blink in unison)
Waiting for IP Address
ETHERNET OK
LAN OK
LOG EMPTY
On
On/Traffic/Off
On/Off
Operational
ETHERNET OK
LAN OK
LOG EMPTY
Blink error code
Off
Off
Hardware failure. See chapter 11
for blink code definitions.
ETHERNET OK
LAN OK
LOG EMPTY
Slow Blink
†
Slow Blink
†
Slow Blink
†
(† All LEDs blink in
unison; pattern same
while awaiting or
performing load)
Firmware Update
Field Wiring Station Manager (RS-232) Port Pin Assignment
Pin No Signal Direction Description
1† DCD IN Data Carrier Detect
2 TX OUT Transmit Data
3 RX IN Receive Data
4 DSR IN Data Set Ready
5 GND Signal Ground
6 DTR OUT Data Terminal Ready
7 CTS IN Clear to Send
8 RTS OUT Ready to Send
9 RI IN Ring Indicator
†
Pin 1 is at the bottom right of the Station Manager port connector
as viewed from the front of the module.